CHAPTER 5: SETTINGS<br />
5.9.4 RTD 11<br />
RTDs 7 through 10 default to “Bearing” RTD type. There are individual alarm and trip<br />
configurations for each RTD. This allows one of the RTDs to be turned off if it malfunctions.<br />
The alarm level, high alarm level and the trip level are normally set slightly above the<br />
normal running temperature, but below the bearing temperature rating. Trip voting has<br />
been added for extra reliability in the event of RTD malfunction. If enabled, a second RTD<br />
must also exceed the trip temperature of the RTD being checked before a trip will be<br />
issued. If the RTD is chosen to vote with itself, the voting feature is disabled. Each RTD<br />
name may be changed if desired.<br />
PATH: SETTINGS S8 RTD TEMPERATURE RTD #11<br />
RTD<br />
#11 []<br />
MESSA<strong>GE</strong><br />
MESSA<strong>GE</strong><br />
MESSA<strong>GE</strong><br />
MESSA<strong>GE</strong><br />
MESSA<strong>GE</strong><br />
MESSA<strong>GE</strong><br />
MESSA<strong>GE</strong><br />
MESSA<strong>GE</strong><br />
MESSA<strong>GE</strong><br />
MESSA<strong>GE</strong><br />
MESSA<strong>GE</strong><br />
MESSA<strong>GE</strong><br />
RTD #11 APPLICA-<br />
TION:<br />
RTD #11 NAME:<br />
RTD #11 ALARM:<br />
Off<br />
ASSIGN ALARM<br />
RELAYS:<br />
RTD #11 ALARM<br />
TEMPERATURE: 80°C<br />
RTD #7 HIGH<br />
ALARM:<br />
HIGH ALARM<br />
RELAYS:<br />
RTD #11 HIGH<br />
ALARM<br />
RTD #11 ALARM<br />
EVENTS: Off<br />
RTD #11 TRIP:<br />
Off<br />
RTD #11 TRIP VOT-<br />
ING:<br />
ASSIGN TRIP<br />
RELAYS:<br />
RTD #11 TRIP<br />
TEMPERATURE: 90°C<br />
Range: Stator, Bearing, Ambient, Other,<br />
None<br />
Range: 8 alphanumeric characters<br />
Range: Off, Latched, Unlatched<br />
Range: Alarm, Alarm & Auxiliary2,<br />
Alarm & Aux2 & Aux3, Alarm &<br />
Auxiliary3, Auxiliary2, Aux2 &<br />
Aux3, Auxiliary3, None<br />
Range: 1 to 250°C in steps of 1<br />
Range: Off, Latched, Unlatched<br />
Range: Alarm, Alarm & Auxiliary2,<br />
Alarm & Aux2 & Aux3, Alarm &<br />
Auxiliary3, Auxiliary2, Aux2 &<br />
Aux3, Auxiliary3, None<br />
Range: 1 to 250°C in steps of 1<br />
Range: On, Off<br />
Range: Off, Latched, Unlatched<br />
Range: RTD #1 to RTD #12<br />
Range: Trip, Trip & Auxiliary2, Trip &<br />
Aux2 & Aux3, Trip & Auxiliary3<br />
Range: 1 to 250°C in steps of 1<br />
RTD 11 defaults to “Other” RTD type. The Other selection allows the RTD to be used to<br />
monitor any temperature that might be required, either for a process or additional<br />
bearings or other. There are individual alarm, high alarm and trip configurations for this<br />
<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 5–73