CHAPTER 5: SETTINGS<br />

5.9.4 RTD 11<br />

RTDs 7 through 10 default to “Bearing” RTD type. There are individual alarm and trip<br />

configurations for each RTD. This allows one of the RTDs to be turned off if it malfunctions.<br />

The alarm level, high alarm level and the trip level are normally set slightly above the<br />

normal running temperature, but below the bearing temperature rating. Trip voting has<br />

been added for extra reliability in the event of RTD malfunction. If enabled, a second RTD<br />

must also exceed the trip temperature of the RTD being checked before a trip will be<br />

issued. If the RTD is chosen to vote with itself, the voting feature is disabled. Each RTD<br />

name may be changed if desired.<br />

PATH: SETTINGS S8 RTD TEMPERATURE RTD #11<br />

RTD<br />

#11 []<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

RTD #11 APPLICA-<br />

TION:<br />

RTD #11 NAME:<br />

RTD #11 ALARM:<br />

Off<br />

ASSIGN ALARM<br />

RELAYS:<br />

RTD #11 ALARM<br />

TEMPERATURE: 80°C<br />

RTD #7 HIGH<br />

ALARM:<br />

HIGH ALARM<br />

RELAYS:<br />

RTD #11 HIGH<br />

ALARM<br />

RTD #11 ALARM<br />

EVENTS: Off<br />

RTD #11 TRIP:<br />

Off<br />

RTD #11 TRIP VOT-<br />

ING:<br />

ASSIGN TRIP<br />

RELAYS:<br />

RTD #11 TRIP<br />

TEMPERATURE: 90°C<br />

Range: Stator, Bearing, Ambient, Other,<br />

None<br />

Range: 8 alphanumeric characters<br />

Range: Off, Latched, Unlatched<br />

Range: Alarm, Alarm & Auxiliary2,<br />

Alarm & Aux2 & Aux3, Alarm &<br />

Auxiliary3, Auxiliary2, Aux2 &<br />

Aux3, Auxiliary3, None<br />

Range: 1 to 250°C in steps of 1<br />

Range: Off, Latched, Unlatched<br />

Range: Alarm, Alarm & Auxiliary2,<br />

Alarm & Aux2 & Aux3, Alarm &<br />

Auxiliary3, Auxiliary2, Aux2 &<br />

Aux3, Auxiliary3, None<br />

Range: 1 to 250°C in steps of 1<br />

Range: On, Off<br />

Range: Off, Latched, Unlatched<br />

Range: RTD #1 to RTD #12<br />

Range: Trip, Trip & Auxiliary2, Trip &<br />

Aux2 & Aux3, Trip & Auxiliary3<br />

Range: 1 to 250°C in steps of 1<br />

RTD 11 defaults to “Other” RTD type. The Other selection allows the RTD to be used to<br />

monitor any temperature that might be required, either for a process or additional<br />

bearings or other. There are individual alarm, high alarm and trip configurations for this<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 5–73