<strong>Digital</strong> Counter<br />

PATH: SETTINGS S3 DIGITAL INPUTS ASSIGNABLE INPUT 1(4)<br />

<br />

ASSIGNABLE [<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

These settings apply only if the INPUT 1(4) FUNCTION is “<strong>Digital</strong> Counter”.<br />

CHAPTER 5: SETTINGS<br />

Once the <strong>Digital</strong> Counter function is chosen for one of the assignable digital inputs, the<br />

settings messages shown here will follow the assignment message. Each closure of the<br />

switch will be counted, by either incrementing or decrementing the counter value. An<br />

alarm may be configured when a certain count is reached. The counter value may be<br />

viewed in the A4 MAINTENANCE <strong>GE</strong>NERAL COUNTERS DIGITAL COUNTER actual<br />

value.<br />

To initialize the counter, program the counter value here and then change the S1 <strong>469</strong> SETUP<br />

CLEAR DATA PRESET DIGITAL COUNTER settings to “Yes”.<br />

For example, a capacitive proximity probe may be used to sense non-magnetic units that<br />

are passing by on a conveyor, glass bottles for instance. The probe could be powered from<br />

the +24 V from the input switch power supply. The NPN transistor output could be taken to<br />

one of the assignable digital inputs configured as a counter.<br />

Tachometer<br />

INPUT 1 FUNCTION:<br />

<strong>Digital</strong> Counter<br />

COUNTER UNITS:<br />

Units<br />

COUNTER PRESET<br />

VALUE: 0<br />

COUNTER TYPE:<br />

Increment<br />

COUNTER<br />

ALARM: Off<br />

Range: See above<br />

PATH: SETTINGS S3 DIGITAL INPUTS ASSIGNABLE INPUT 1(4)<br />

<br />

ASSIGNABLE [<br />

MESSA<strong>GE</strong><br />

ASSIGN ALARM<br />

RELAYS:<br />

COUNTER ALARM<br />

LEVEL: 100<br />

COUNTER ALARM<br />

PICKUP: Over<br />

COUNTER ALARM<br />

EVENTS: Off<br />

INPUT 1 FUNCTION:<br />

Tachometer<br />

RATED SPEED:<br />

3600 RPM<br />

Range: 6 alphanumeric characters<br />

Range: 0 to 1000000000 in steps of 1<br />

Range: Increment, Decrement<br />

Range: Off, Latched, Unlatched<br />

Range: Alarm, Alarm & Auxiliary2,<br />

Alarm & Aux2 & Aux3, Alarm &<br />

Auxiliary3, Auxiliary2, Aux2 &<br />

Aux3, Auxiliary3, None<br />

Range: 0 to 1000000000 in steps of 1<br />

Range: Over, Under<br />

Range: On, Off<br />

Range: See above<br />

Range: 100 to 7200 RPM in steps of 1<br />

5–30 <strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL