CHAPTER 5: SETTINGS<br />

Note<br />

5.10.4 Frequency<br />

The <strong>469</strong> can detect the phase rotation of the three phase voltage. If the Phase Reversal<br />

feature is turned on when all 3 phase voltages are greater than 50% motor nameplate<br />

voltage, and the phase rotation of the three phase voltages is not the same as the settings,<br />

a trip and block start will occur in 500 to 700 ms.<br />

This feature does not work when single VT operation is enabled.<br />

PATH: SETTINGS S9 VOLTA<strong>GE</strong> ELEM. FREQUENCY<br />

<br />

FREQUENCY [<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

FREQUENCY<br />

ALARM: Off<br />

ASSIGN ALARM<br />

RELAYS:<br />

OVER FREQUENCY<br />

ALARM LEVEL:<br />

UNDER FREQUENCY<br />

ALARM LEVEL:<br />

FREQUENCY<br />

ALARM DELAY: 1.0<br />

FREQUENCY<br />

ALARM EVENTS: Off<br />

FREQUENCY<br />

TRIP: Off<br />

ASSIGN TRIP<br />

RELAYS:<br />

OVER FREQUENCY<br />

TRIP LEVEL: 60.50<br />

UNDER FREQUENCY<br />

TRIP LEVEL: 59.50<br />

FREQUENCY<br />

TRIP DELAY: 1.0 s<br />

Range: Off, Latched, Unlatched<br />

Range: Alarm, Alarm & Auxiliary2,<br />

Alarm & Aux2 & Aux3, Alarm &<br />

Auxiliary3, Auxiliary2, Aux2 &<br />

Aux3, Auxiliary3, None<br />

Range: 25.01 to 70.00 Hz in steps of<br />

0.01<br />

Range: 20.00 to 60.00 Hz in steps of<br />

0.01<br />

Range: 0.0 to 60.0 s in steps of 0.1<br />

Range: On, Off<br />

Range: Off, Latched, Unlatched<br />

Range: Trip, Trip & Auxiliary2, Trip &<br />

Aux2 & Aux3, Trip & Auxiliary3<br />

Range: 25.01 to 70.00 Hz in steps of<br />

0.01<br />

Range: 20.00 to 60.00 Hz in steps of<br />

0.01<br />

Range: 0.0 to 60.0 s in steps of 0.1<br />

Once the frequency of the phase AN or AB voltage (depending on wye or delta connection)<br />

is out of range of the overfrequency and underfrequency settings, a trip or alarm will occur.<br />

This feature may be useful for load shedding applications on large motors. It could also be<br />

used to load shed an entire feeder if the trip was assigned to an upstream breaker.<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 5–79