2.2.3 Protection<br />

OUTPUT RELAYS<br />

CHAPTER 2: INTRODUCTION<br />

power factor; 3-phase real (kW), apparent (kVA), and<br />

reactive (kvar) power; thermal capacity used; relay<br />

lockout time, current demand; kvar, kW, and kVA demand;<br />

motor load, torque<br />

<strong>Relay</strong> contacts are unsafe to touch when the <strong>469</strong> is energized! If the output relay<br />

contacts are required for low voltage accessible applications, it is the customer's<br />

responsibility to ensure proper insulation levels.<br />

Configuration: .................................................6 Electromechanical Form C<br />

Contact material: ..........................................silver alloy<br />

Operate time: ..................................................10 ms<br />

Make/carry:.......................................................10 A continuous<br />

30 A for 0.2 s<br />

Max ratings for 100000 operations:<br />

DC<br />

RESISTIVE<br />

DC<br />

INDUCTIVE L/<br />

R=40ms<br />

AC<br />

RESISTIVE<br />

AC<br />

INDUCTIVE<br />

P.F.=0.4<br />

VOLTA<strong>GE</strong> BREAK MAX.<br />

LOAD<br />

30 V 10 A 300 Ω<br />

125 V 0.5 A 62.5 Ω<br />

250 V 0.3 A 75 Ω<br />

30 V 5 A 150 Ω<br />

125 V 0.25 A 31.3 Ω<br />

250 V 0.15 A 37.5 Ω<br />

120 V 10 A 2770 VA<br />

250 V 10 A 2770 VA<br />

120 V 4 A 480 VA<br />

250 V 3 A 750 VA<br />

ACCELERATION TIMER<br />

Pickup: .................................................................transition of no phase current to > overload pickup<br />

Dropout:..............................................................when current falls below overload pickup<br />

Time delay:........................................................1.0 to 250.0 s in steps of 0.1<br />

Timing accuracy: ...........................................±100 ms or ±0.5% of total time<br />

Elements:............................................................Trip<br />

CURRENT UNBALANCE<br />

Unbalance: ........................................................I 2 /I 1 if I avg > FLA<br />

I 2 /I 1 × I avg /FLA if I avg < FLA<br />

Range:..................................................................0 to 100% UB in steps of 1<br />

Pickup level:.......................................................4 to 40% UB in steps of 1<br />

Time delay:........................................................1 to 60 s in steps of 1<br />

Pickup accuracy: ...........................................±2%<br />

Timing accuracy: ...........................................±0.5 s or ± 0.5% of total time<br />

Elements:............................................................Trip and Alarm<br />

FREQUENCY<br />

Req’d voltage: .................................................>30% of full scale in phase A<br />

Overfrequency pickup: ...............................25.01 to 70.00 Hz in steps of 0.01<br />

Underfrequency pickup: ............................20.00 to 60.00 Hz in steps of 0.01<br />

Accuracy:............................................................±0.02 Hz<br />

Time delay:........................................................0.0 to 60.0 s in steps of 0.1<br />

2–8 <strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL