06.05.2013 Views

Multilin 469 Motor Management Relay ... - GE Digital Energy

Multilin 469 Motor Management Relay ... - GE Digital Energy

Multilin 469 Motor Management Relay ... - GE Digital Energy

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

5.3.4 Communications Control<br />

CHAPTER 5: SETTINGS<br />

Enter the nominal system frequency here. These settings allow the <strong>469</strong> to determine the<br />

internal sampling rate for maximum accuracy.<br />

The <strong>469</strong> may be used on variable frequency drives when the NOMINAL SYSTEM FREQUENCY<br />

is set to “Variable”. All of the elements function in the same manner with the following<br />

exceptions: the ratio of negative to positive-sequence current is calculated from 0 to 30%,<br />

not 40%, and the voltage and power elements work properly if the voltage waveform is<br />

approximately sinusoidal. An unfiltered voltage waveform from a pulse width modulated<br />

drive cannot be measured accurately; however, the current waveform is approximately<br />

sinusoidal and can be measured accurately. All current elements will function properly.<br />

Note, however, that undervoltage and underfrequency elements will not work<br />

instantaneously using variable frequency. If “Variable” is chosen, the filtering algorithm<br />

increases the trip and alarm times by up to 270 ms when the level is close to the threshold.<br />

If the level exceeds the threshold by a significant amount, trip and alarm times will<br />

decrease until they match the programmed delay. The exceptions to this increased time<br />

are the short circuit, ground fault, and differential elements which will trip as per<br />

specification.<br />

If the sequence of phase rotation for a given plant is ACB rather than the standard ABC, the<br />

SYSTEM PHASE SEQUENCE settings may be used to accommodate this. This settings allows<br />

the <strong>469</strong> to properly calculate phase reversal, negative sequence, and power quantities. The<br />

SPEED2 PHASE SEQUENCE can be programmed to accommodate the reversed motor<br />

rotation at Speed2 and is seen only if two-speed motor protection is enabled.<br />

PATH: SETTINGS S2 SYSTEM SETUP SERIAL COMM. CONTROL<br />

SERIAL<br />

COMM. []<br />

MESSA<strong>GE</strong><br />

SERIAL COMMUNICA-<br />

TION<br />

ASSIGN START CON-<br />

TROL<br />

Range: On, Off<br />

Range: Auxiliary2, Aux2 & Aux3,<br />

Auxiliary3<br />

If enabled, motor starting and stopping is possible via any of the three <strong>469</strong> communication<br />

ports. Refer to <strong>GE</strong> publication <strong>GE</strong>K-106491: <strong>469</strong> Communications Guide for command<br />

formats. When a stop command is issued, the 1 TRIP relay is activated for 1 second to<br />

complete the trip coil circuit for a breaker application or break the contact coil circuit for a<br />

contactor application. When a start command is issued, the auxiliary relay assigned for<br />

starting control is activated for 1 second to complete the close coil circuit for a breaker<br />

application or complete the start control circuit for a contactor application. A contactor<br />

sealing contact would be used to maintain the circuit.<br />

For details on issuing a start or stop command via communications, refer to <strong>GE</strong> publication<br />

<strong>GE</strong>K-106491: <strong>469</strong> Communications Guide.<br />

5–20 <strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!