Note<br />

<strong>469</strong><br />

BLOCK TRIP STOP START<br />

3 x FLA<br />

Transition<br />

Level<br />

FIGURE 5–1: Reduced Voltage Start Contactor Control Circuit<br />

FLA<br />

MOTOR<br />

AMPS<br />

(% FLA)<br />

808725A1.CDR<br />

FIGURE 5–2: Reduced Voltage Starting Current Characteristic<br />

CHAPTER 5: SETTINGS<br />

808724A2.CDR<br />

If this feature is used, the Starter Status Switch input must be either from a common<br />

control contact or a parallel combination of Auxiliary ‘a’ contacts or a series combination<br />

of Auxiliary ‘b’ contacts from the reduced voltage contactor and the full voltage contactor.<br />

Once transition is initiated, the <strong>469</strong> assumes the motor is still running for at least 2<br />

seconds. This prevents the <strong>469</strong> from recognizing an additional start if motor current goes<br />

to zero during an open transition.<br />

5–22 <strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL<br />

<strong>469</strong><br />

3AUX<br />

CC2 SEAL IN<br />

CC1<br />

CC1<br />

SEAL IN<br />

CC2<br />

When the currrent falls below<br />

the Transition Level and/or the<br />

Timer expires, the Auxiliary<br />

<strong>Relay</strong> activates for 1 second<br />

Transition Time<br />

REDUCED VOLTA<strong>GE</strong><br />

CONTACTOR<br />

FULL VOLTA<strong>GE</strong><br />

CONTACTOR<br />

signifies<br />

Open Transition<br />

TIME