06.05.2013 Views

Multilin 469 Motor Management Relay ... - GE Digital Energy

Multilin 469 Motor Management Relay ... - GE Digital Energy

Multilin 469 Motor Management Relay ... - GE Digital Energy

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

CHAPTER 5: SETTINGS<br />

If the undervoltage alarm feature is enabled, an alarm will occur once the magnitude of<br />

either Vab, Vbc, or Vca falls below the pickup level while running or starting for a period of<br />

time specified by the delay (note that pickup levels are multiples of motor nameplate<br />

voltage). The running pickup level also applies when the motor is stopped and the U/V<br />

ACTIVE ONLY IF BUS ENERGIZED settings is programmed to “No”.<br />

Undervoltage trips can be set for single-phase or three-phase conditions. If undervoltage<br />

tripping is enabled, and the UNDERVOLTA<strong>GE</strong> TRIP MODE is set for “3-Phase”, a trip will occur<br />

only when the magnitude of all three phases falls below the pickup level while running or<br />

starting for a period of time specified by the time delay. On the other hand, if undervoltage<br />

trip is enabled, and the UNDERVOLTA<strong>GE</strong> TRIP MODE is set for “1-Phase”, a trip will occur<br />

once the magnitude of either Vab, Vbc, or Vca falls below the pickup level while running or<br />

starting for a period of time specified by the time delay. Note that pickup levels are<br />

multiples of motor nameplate voltage. The running pickup level also applies when the<br />

motor is stopped, and the U/V ACTIVE ONLY IF BUS ENERGIZED settings is programmed to<br />

“No”.<br />

An undervoltage on a running motor with a constant load results in increased current. The<br />

relay thermal model typically picks up this condition and provides adequate protection.<br />

However, this settings may be used in conjunction with the time delay to provide additional<br />

protection that may be programmed for advance warning by tripping.<br />

Attempting to start a large motor when the supply voltage is down may also be<br />

undesirable. An undervoltage of significant proportion that persists while starting a motor<br />

may prevent the motor from reaching rated speed. This may be especially critical for a<br />

synchronous motor. As such, this feature may be used in with a time delay to provide<br />

protection for undervoltage conditions before and during starting.<br />

In the event of system problems causing asymmetrical voltage conditions where at least<br />

one voltage remains above pickup, an Alarm condition will occur, indicating that the<br />

voltage on at least one phase is below acceptable levels. The trip relay will not be<br />

energized unless the UNDERVOLTA<strong>GE</strong> TRIP MODE is set to “1-Phase”. The factory default<br />

setting for UNDERVOLTA<strong>GE</strong> TRIP MODE is “1-Phase”.<br />

To prevent for nuisance undervoltage trips due to VT Fuse Failure, set the UNDERVOLTA<strong>GE</strong><br />

TRIP MODE to “3-Phase”. The alarm relay will be energized in the event of a single-phase<br />

undervoltage, which can also be an indication of a potential VT fuse failure. Typically a fuse<br />

failure is detected when there are significant levels of negative-sequence voltage,<br />

indicating voltage unbalance due to the loss of one phase, without correspondingly<br />

significant levels of negative-sequence current, indicating current unbalance, measured at<br />

the output CTs.<br />

If the conditions for Fuse Failure exist, an alarm will occur after a time delay due to an<br />

undervoltage condition in at least one phase. If the motor is running, the voltage in the<br />

faulted phase will be zero, and the measured load current should not indicate a significant<br />

amount of negative or unbalance currents. Therefore the motor can be kept in service until<br />

the opportunity to replace the faulty fuse is available.<br />

If the alarm is caused by an abnormal system conditions, a significant amount of<br />

unbalance current will be present. If the condition is not detected on time, the unbalance<br />

function or the underpower element will trip the motor.<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 5–77

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!