CHAPTER 5: SETTINGS<br />

5.3.2 Voltage Sensing<br />

5.3.3 Power System<br />

PHASE CT PRIMARY: “350”<br />

MOTOR FULL LOAD AMPS: “330”<br />

GROUND CT: “50:0.025”<br />

PATH: SETTINGS S2 SYSTEM SETUP VOLTA<strong>GE</strong> SENSING<br />

<br />

VOLTA<strong>GE</strong> [<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

VT CONNECTION<br />

TYPE:<br />

ENABLE SINGLE VT<br />

OPERATION: OFF<br />

The manner in which the voltage transformers are connected must be entered here. A<br />

value of “None” for VT CONNECTION TYPE indicates that no voltage measurement is<br />

required. Note that phase reversal is disabled for single VT operation. All voltages are<br />

assumed balanced. Also, frequency is only available for AN or AB connections.<br />

The ENABLE SINGLE VT OPERATION settings is seen only if the VT CONNECTION TYPE is<br />

“Open Delta” or “Wye”.<br />

If voltage measurements are to be made, the turns ratio of the voltage transformers must<br />

be entered. The VOLTA<strong>GE</strong> TRANSFORMER RATIO must be chosen such that the secondary<br />

voltage of the VTs is between 40 and 240 V when the primary is at MOTOR NAMEPLATE<br />

VOLTA<strong>GE</strong>. All voltage protection features that require a level settings are programmed as a<br />

percent of the MOTOR NAMEPLATE VOLTA<strong>GE</strong> or rated voltage, where MOTOR NAMEPLATE<br />

VOLTA<strong>GE</strong> represents the rated design voltage line to line.<br />

For example, given the motor nameplate voltage as 4160 V and the VTs are 4160/120<br />

Open Delta, set the voltage sensing settings as follows:<br />

VT CONNECTION TYPE: “Open Delta”<br />

VT RATIO: “34.67:1”<br />

MOTOR NAMEPLATE VOLTA<strong>GE</strong>: “4160”<br />

PATH: SETTINGS S2 SYSTEM SETUP POWER SYSTEM<br />

<br />

POWER [<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

VOLTA<strong>GE</strong> TRANS-<br />

FORMER<br />

MOTOR NAMEPLATE<br />

VOLTA<strong>GE</strong>: 4000 V<br />

NOMINAL SYSTEM<br />

FREQUENCY: 60 Hz<br />

SYSTEM PHASE<br />

SEQUENCE: ABC<br />

SPEED2 PHASE<br />

SEQUENCE: ABC<br />

Range: Open Delta, Wye, None<br />

Range: AN, BN, CN, OFF or AB, BC, OFF<br />

Range: 1.00:1 to 300.00:1 in steps of<br />

0.01<br />

Range: 100 to 36000 V in steps of 1<br />

Range: 50 Hz, 60 Hz, Variable<br />

Range: ABC, ACB<br />

Range: ABC, ACB<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 5–19