06.05.2013 Views

Multilin 469 Motor Management Relay ... - GE Digital Energy

Multilin 469 Motor Management Relay ... - GE Digital Energy

Multilin 469 Motor Management Relay ... - GE Digital Energy

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

CHAPTER 1: <strong>GE</strong>TTING STARTED<br />

For current transformers, make the following change in the S2 SYSTEM SETUP CURRENT<br />

SENSING settings page:<br />

PHASE CT PRIMARY: “400 A”<br />

MOTOR FULL LOAD AMPS FLA: “348 A”<br />

GROUND CT: “5 A Secondary”<br />

GROUND CT PRIMARY: “50 A”<br />

PHASE DIFFERENTIAL CT: “None”<br />

ENABLE 2-SPEED MOTOR PROTECTION: “No”<br />

For current transformers, make the following change in the S2 SYSTEM SETUP VOLTA<strong>GE</strong><br />

SENSING settings page:<br />

VT CONNECTION TYPE: “Open Delta”<br />

ENABLE SINGLE VT OPERATION: “Off”<br />

VOLTA<strong>GE</strong> TRANSFORMER RATIO: “5 : 1”<br />

(for a 600 V system, 600/120 V = 5, where 5 is the VT ratio)<br />

MOTOR NAMEPLATE VOLTA<strong>GE</strong>: “575 V”<br />

The <strong>469</strong> <strong>Motor</strong> <strong>Management</strong> <strong>Relay</strong> was designed with the ability to display primary system<br />

values. Current and voltage measurements are performed at secondary levels, which the<br />

relay transforms to primary values using CT and VT ratios, system voltage, as well as the<br />

nominal secondary values.<br />

In the case of the phase CTs, configuring the relay for current measurements is simple and<br />

it only requires inputting the CT primary current. Phase CT inputs can be 1 A or 5 A, and<br />

they must be specified when the relay is purchased.<br />

There is more flexibility with regards to Ground CT inputs, as well as VT inputs, where<br />

nominal values are not required ahead of time, before the relay is ordered; therefore more<br />

settings are needed to set the relay for measurements.<br />

Make the following change in the S2 SYSTEM SETUP POWER SYSTEM settings page to<br />

reflect the power system:<br />

NOMINAL SYSTEM FREQUENCY: “60 Hz”<br />

SYSTEM PHASE SEQUENCE: “ABC”<br />

The example calls for remote control via serial communications, received from the master<br />

station, through the RTU. <strong>Motor</strong> starting and stopping is possible via any of the three <strong>469</strong><br />

communication ports.<br />

When a start command is issued, the auxiliary relay assigned for starting control is<br />

activated for 1 second to complete the close coil circuit for a breaker application, or<br />

complete the start control circuit for a contactor application. A contactor sealing contact<br />

would be used to maintain the circuit. For details on issuing a start or stop command via<br />

communications, refer to the <strong>GE</strong> Publication <strong>GE</strong>K-106491: <strong>469</strong> Communications Guide.<br />

Make the following changes to the communications settings in the S2 SYSTEM SETUP <br />

SERIAL COMM. CONTROL page.<br />

SERIAL COMMUNICATION CONTROL: “On”<br />

ASSIGN START CONTROL RELAYS: “Auxiliary2”<br />

The Auxiliary 2 relay will be used to start the motor. Note that this auxiliary relay can not be<br />

used for any other application.<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 1–31

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!