06.05.2013 Views

Multilin 469 Motor Management Relay ... - GE Digital Energy

Multilin 469 Motor Management Relay ... - GE Digital Energy

Multilin 469 Motor Management Relay ... - GE Digital Energy

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

CHAPTER 5: SETTINGS<br />

The following settings appear when the relay is ordered with the DeviceNet (D) option.<br />

PATH: SETTINGS S1 <strong>469</strong> SETUP COMMUNICATIONS<br />

<br />

COMMUNICATIONS [<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

SLAVE ADDRESS:<br />

254<br />

COMPUTER RS485<br />

BAUD RATE: 9600<br />

COMPUTER RS485<br />

PARITY: None<br />

FRONT PORT RS232<br />

BAUD RATE: 19200<br />

DEVICENET MAC ID:<br />

1<br />

DEVICENET<br />

BAUD RATE: 125K<br />

Enter the dedicated MAC ID and baud rate as per the DeviceNet design (Refer to <strong>GE</strong>K-<br />

106491C: <strong>469</strong> Communications Guide). The DeviceNet option is implemented by the <strong>469</strong><br />

relay using the AnyBus-S DeviceNet (HMS) module as a communication adapter. The<br />

module is ODVA certified and acts as a server between the relay and the DeviceNet<br />

network.<br />

The following master/slave connection objects are supported by the <strong>469</strong> DeviceNet<br />

implementation:<br />

• Explicit Messaging Connection<br />

• Poll I/O Connection<br />

• Change of State or Cyclic I/O Connection<br />

The following objects have been implemented:<br />

Range: 1 to 254 in steps of 1<br />

Range: 300, 1200, 2400, 4800, 9600,<br />

19200<br />

Range: None, Odd, Even<br />

Range: 300, 1200, 2400, 4800, 9600,<br />

19200<br />

Range: 0 to 63<br />

Range: 125K, 250K, 500K<br />

Object<br />

DeviceNet objects<br />

Class<br />

Identity object 01h<br />

Message Router object 02h<br />

DeviceNet object 03h<br />

Assembly object 04h<br />

Connection object 05h<br />

Acknowledge Handler object<br />

<strong>469</strong> specific objects<br />

2Bh<br />

I/O Data Input Mapping object A0h<br />

Parameter Data Input Mapping object B0h<br />

Refer to publication <strong>GE</strong>K-106491C: <strong>469</strong> Communications Guide for additional details<br />

on the DeviceNet implementation.<br />

5–12 <strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!