6.4.2 Average <strong>Motor</strong> Load<br />

PATH: ACTUAL VALUES A3 LEARNED DATA AVERA<strong>GE</strong> MOTOR LOAD<br />

<br />

AVERA<strong>GE</strong> [<br />

]<br />

MOTOR LOAD<br />

6.4.3 RTD Maximums<br />

CHAPTER 6: ACTUAL VALUES<br />

The <strong>469</strong> can learn the average motor load over a period of time. This time is specified by<br />

the S1 <strong>469</strong> SETUP PREFERENCES AVERA<strong>GE</strong> MOTOR LOAD CALC. PERIOD settings<br />

(default 15 minutes). The calculation is a sliding window and is ignored during motor<br />

starting.<br />

PATH: ACTUAL VALUES A3 LEARNED DATA RTD MAXIMUMS<br />

RTD<br />

MAXIMUMS []<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

AVERA<strong>GE</strong> MOTOR<br />

LOAD<br />

LEARNED: 0.00 x<br />

FLA<br />

RTD #1<br />

MAX. TEMP.: 40°C<br />

RTD #2<br />

MAX. TEMP.: 40°C<br />

RTD #3<br />

MAX. TEMP.: 40°C<br />

RTD #4<br />

MAX. TEMP.: 40°C<br />

RTD #5<br />

MAX. TEMP.: 40°C<br />

RTD #6<br />

MAX. TEMP.: 40°C<br />

RTD #7<br />

MAX. TEMP.: 40°C<br />

RTD #8<br />

MAX. TEMP.: 40°C<br />

RTD #9<br />

MAX. TEMP.: 40°C<br />

RTD #10<br />

MAX. TEMP.: 40°C<br />

RTD #11<br />

MAX. TEMP.: 40°C<br />

RTD #12<br />

MAX. TEMP.: 40°C<br />

Range: 0.00 to 20.00<br />

Range: –50 to 250°C<br />

Range: –50 to 250°C<br />

Range: –50 to 250°C<br />

Range: –50 to 250°C<br />

Range: –50 to 250°C<br />

Range: –50 to 250°C<br />

Range: –50 to 250°C<br />

Range: –50 to 250°C<br />

Range: –50 to 250°C<br />

Range: –50 to 250°C<br />

Range: –50 to 250°C<br />

Range: –50 to 250°C<br />

The <strong>469</strong> will learn the maximum temperature for each RTD. This information can be<br />

cleared using the S1 <strong>469</strong> SETUP CLEAR DATA CLEAR RTD MAXIMUMS settings.<br />

6–28 <strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL