CHAPTER 1: <strong>GE</strong>TTING STARTED<br />

<br />

SETTINGS [<br />

To set the ground CT ratings, modify the S2 SYSTEM SETUP CURRENT SENSING <br />

GROUND CT and the S2 SYSTEM SETUP CURRENT SENSING GROUND CT PRIMARY<br />

settings as shown below.<br />

Press MESSA<strong>GE</strong> or ENTER<br />

<br />

SETTINGS [<br />

Press MESSA<strong>GE</strong> <br />

<br />

SETTINGS [<br />

Press<br />

MESSA<strong>GE</strong> <br />

or ENTER<br />

Press the MENU key until the relay displays the Settings menu<br />

header.<br />

<br />

CURRENT [<br />

Press<br />

MESSA<strong>GE</strong> <br />

or ENTER<br />

PHASE CT PRIMARY:<br />

600 A<br />

Press MOTOR FULL LOAD<br />

MESSA<strong>GE</strong> AMPS<br />

Press GROUND CT:<br />

MESSA<strong>GE</strong> <strong>Multilin</strong> CT 50/<br />

Press the VALUE keys until GROUND CT:<br />

“5 A Secondary” is displayed. 5 A Secondary<br />

Press the ENTER key to store the NEW SETTINGS<br />

settings. HAS<br />

Press GROUND CT PRI-<br />

MESSA<strong>GE</strong> MARY:<br />

Press the VALUE keys until 50 A is GROUND CT PRIdisplayed,<br />

or enter the value directly via MARY:<br />

the numeric keypad.<br />

Press the ENTER key to store the NEW SETTINGS<br />

settings. HAS<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 1–13