5.10 S9 Voltage Elements<br />

5.10.1 Undervoltage<br />

PATH: SETTINGS S9 VOLTA<strong>GE</strong> ELEM. UNDERVOLTA<strong>GE</strong><br />

<br />

UNDERVOLTA<strong>GE</strong> [<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

U/V ACTIVE ONLY<br />

IF<br />

UNDERVOLTA<strong>GE</strong><br />

ALARM: Off<br />

ASSIGN ALARM<br />

RELAYS:<br />

UNDERVOLTA<strong>GE</strong><br />

ALARM<br />

STARTING U/V<br />

ALARM<br />

UNDERVOLTA<strong>GE</strong><br />

ALARM<br />

UNDERVOLTA<strong>GE</strong><br />

ALARM<br />

UNDERVOLTA<strong>GE</strong><br />

TRIP: Off<br />

UNDERVOLTA<strong>GE</strong> TRIP<br />

MODE: 1-Phase<br />

ASSIGN TRIP<br />

RELAYS:<br />

UNDERVOLTA<strong>GE</strong> TRIP<br />

PICKUP: 0.80 x<br />

STARTING U/V TRIP<br />

PICKUP: 0.80 x<br />

UNDERVOLTA<strong>GE</strong> TRIP<br />

DELAY: 3.0 s<br />

Range: No, Yes<br />

CHAPTER 5: SETTINGS<br />

Range: Off, Latched, Unlatched<br />

Range: Alarm, Alarm & Auxiliary2,<br />

Alarm & Aux2 & Aux3, Alarm &<br />

Auxiliary3, Auxiliary2, Aux2 &<br />

Aux3, Auxiliary3, None<br />

Range: 0.60 to 0.99 x RATED in steps of<br />

0.01<br />

Range: 0.60 to 1.00 x RATED in steps of<br />

0.01. Enter “1.00” to turn this<br />

function off.<br />

Range: 0.0 to 60.0 s in steps of 0.1<br />

Range: On, Off<br />

Range: Off, Latched, Unlatched<br />

Range: 1-Phase, 3-Phase<br />

Range: Trip, Trip & Auxiliary2, Trip &<br />

Aux2 & Aux3, Trip & Auxiliary3<br />

Range: 0.60 to 0.99 x RATED in steps of<br />

0.01<br />

Range: 0.60 to 1.00 x RATED in steps of<br />

0.01. Enter “1.00” to turn this<br />

function off.<br />

Range: 0.0 to 60.0 s in steps of 0.1<br />

The U/V ACTIVE ONLY IF BUS ENERGIZED settings may be used to prevent nuisance alarms<br />

or trips when the bus is not energized. If this settings is programmed to “Yes”, at least one<br />

voltage must be greater than 20% of the nominal nameplate voltage rating for any alarm/<br />

trip. If the load is high inertia, it may be desirable to trip the motor off-line or prevent it from<br />

starting in the event of a total loss of line voltage. Programming “No” for this settings<br />

ensures that the motor is tripped and may be restarted only after the bus is re-energized.<br />

5–76 <strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL