CHAPTER 5: SETTINGS<br />

bits, while parity is optional. The computer RS485 port is a general purpose port for<br />

connection to a DCS, PLC, or PC. The auxiliary RS485 port may be used for redundancy or, it<br />

may be used to talk to auxiliary <strong>GE</strong> <strong>Multilin</strong> devices. The RS485 COM2 port is disabled if the<br />

Ethernet or DeviceNet option is ordered.<br />

Ethernet Communications<br />

The following settings appear when the relay is ordered with the Ethernet (T) option.<br />

PATH: SETTINGS S1 <strong>469</strong> SETUP COMMUNICATIONS<br />

<br />

COMMUNICATIONS [<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

The IP addresses are used with the Modbus protocol (Refer to <strong>GE</strong>K-106491C: <strong>469</strong><br />

Communications Guide). Enter the dedicated IP, subnet IP, and gateway IP addresses<br />

provided by the network administrator.<br />

To ensure optimal response from the relay, the typical connection timeout should be set as<br />

indicated in the following table:<br />

TCP/IP sessions Timeout setting<br />

up to 2 2 seconds<br />

up to 4 3 seconds<br />

DeviceNet Communications<br />

SLAVE ADDRESS:<br />

254<br />

COMPUTER RS485<br />

BAUD RATE: 9600<br />

COMPUTER RS485<br />

PARITY: None<br />

FRONT PORT RS232<br />

BAUD RATE: 19200<br />

IP ADDRESS:<br />

0.0.0.0<br />

SUBNET IP MASK:<br />

255.255.255.000<br />

GATEWAY IP<br />

ADDRESS:<br />

(Refer to <strong>GE</strong>K-106491C: <strong>469</strong> Communications Guide)<br />

Range: 1 to 254 in steps of 1<br />

Range: 300, 1200, 2400, 4800, 9600,<br />

19200<br />

Range: None, Odd, Even<br />

Range: 300, 1200, 2400, 4800, 9600,<br />

19200<br />

Range: standard IP address format<br />

Range: standard IP address format<br />

Range: standard IP address format<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 5–11