7.2.3 Ground and Differential Accuracy Test<br />

CHAPTER 7: TESTING<br />

The <strong>469</strong> specification for differential current and 1 A/5 A ground current input accuracy is<br />

±0.5% of 1 × CT for the 5 A input and 0.5% of 5 × CT for the 1 A input. Perform the steps<br />

below to verify accuracy.<br />

5A Input<br />

Alter the following settings:<br />

S2 SYSTEM SETUP CURRENT SENSING GROUND CT: “5A Secondary”<br />

S2 SYSTEM SETUP CURRENT SENSING GROUND CT PRIMARY: “1000 A”<br />

S2 SYSTEM SETUP CURRENT SENSING PHASE DIFFERENTIAL CT: “5A Secondary”<br />

S2 SYSTEM SETUP CURRENT SENSING PHASE DIFFERENTIAL CT PRIMARY: “1000 A”<br />

1A Input<br />

Measured values should be ±5 A.<br />

INJECTED<br />

CURRENT<br />

5 A UNIT<br />

EXPECTED<br />

VOLTA<strong>GE</strong><br />

READING<br />

Inject the values shown in the table below into one phase only.<br />

Verify accuracy of the measured values.<br />

View the measured values in:<br />

EXPECTED<br />

CURRENT<br />

READING<br />

0.5 A 100 A<br />

1.0 A 200 A<br />

2.5 A 500 A<br />

5.0 A 1000 A<br />

A2 METERING DATA CURRENT METERING<br />

Alter the following settings:<br />

S2 SYSTEM SETUP CURRENT SENSING GROUND CT: “1A Secondary”<br />

S2 SYSTEM SETUP CURRENT SENSING GROUND CT PRIMARY: “1000 A”<br />

S2 SYSTEM SETUP CURRENT SENSING PHASE DIFFERENTIAL CT: “1A Secondary”<br />

S2 SYSTEM SETUP CURRENT SENSING PHASE DIFFERENTIAL CT PRIMARY: “1000 A”<br />

Measured values should be ±25 A.<br />

MEASURED<br />

VOLTA<strong>GE</strong> A-N<br />

MEASURED<br />

GROUND<br />

CURRENT<br />

Inject the values shown below into one phase only.<br />

Verify accuracy of the measured values.<br />

View the measured values in:<br />

MEASURED<br />

VOLTA<strong>GE</strong> B-N<br />

MEASURED<br />

VOLTA<strong>GE</strong> C-N<br />

MEASURED DIFFERENTIAL<br />

CURRENT<br />

PHASE A PHASE B PHASE C<br />

7–4 <strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL