CHAPTER 6: ACTUAL VALUES<br />

The EnerVista <strong>469</strong> Setup software displays the following screen for A2 METERING DATA <br />

PHASORS values:<br />

Pressing the “View” button displays the following screen:<br />

The following phasor diagram illustrates the vector diagram of our example. By definition,<br />

power factor is the cosine of the angle between the phase to neutral voltages and the<br />

corresponding phase current. In this example, 18.2° is the angle between Van and Ia, Vbn<br />

and Ib, and Vcn and Ic. Since the relay is measuring phase-phase quantities, and Vab is the<br />

reference phasor, the angle displayed by the relay takes into consideration the 30° angle<br />

between phase-phase and phase-neutral voltages.<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 6–21