5.6.2 Thermal Model<br />

PATH: SETTINGS S5 THERMAL MODEL THERMAL MODEL<br />

<br />

THERMAL [<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

SELECT CURVE<br />

STYLE:<br />

OVERLOAD PICKUP<br />

LEVEL: 1.01 x FLA<br />

ASSIGN TRIP<br />

RELAYS:<br />

UNBALANCE BIAS<br />

K FACTOR: 0<br />

COOL TIME CON-<br />

STANT<br />

COOL TIME CON-<br />

STANT<br />

HOT/COLD SAFE<br />

STALL RATIO: 1.00<br />

ENABLE RTD<br />

BIASING: No<br />

RTD BIAS<br />

MINIMUM: 40°C<br />

RTD BIAS CENTER<br />

POINT: 130°C<br />

RTD BIAS<br />

MAXIMUM: 155°C<br />

THERMAL CAPACITY<br />

ALARM: Off<br />

ASSIGN ALARM<br />

RELAYS:<br />

THERMAL CAP.<br />

ALARM<br />

THERMAL CAPACITY<br />

ALARM EVENTS: Off<br />

CHAPTER 5: SETTINGS<br />

Range: Standard, Custom, Voltage<br />

Dependent<br />

Range: 1.01 to 1.25 in steps of 0.01<br />

Range: Trip, Trip & Aux2, Trip & Aux2 &<br />

Aux3, Trip & Aux3<br />

Range: 0 to 19 in steps of 1. (0 defeats<br />

this feature)<br />

Range: 1 to 1000 min. in steps of 1<br />

Range: 1 to 1000 min. in steps of 1<br />

Range: 0.01 to 1.00 in steps of 0.01<br />

Range: Yes, No<br />

Range: 0°C to RTD BIAS CENTER value<br />

in steps of 1<br />

Range: RTD BIAS MINIMUM value to<br />

RTD BIAS MAXMIMUM value<br />

in steps of 1<br />

Range: RTD BIAS CENTER value to<br />

250°C in steps of 1<br />

Range: Off, Latched, Unlatched<br />

Range: Alarm, Alarm & Auxiliary2,<br />

Alarm & Aux2 & Aux3, Alarm &<br />

Auxiliary3, Auxiliary2, Aux2 &<br />

Aux3, Auxiliary3, None<br />

Range: 10 to 100% in steps of 1<br />

Range: On, Off<br />

The primary protective function of the <strong>469</strong> is the thermal model. It consists of five key<br />

elements: the overload curve and overload pickup level, the unbalance biasing of the<br />

motor current while the motor is running, the motor cooling time constants, and the<br />

biasing of the thermal model based on Hot/Cold motor information and measured stator<br />

temperature. Each of these elements are described in detail in the sections that follow.<br />

The <strong>469</strong> integrates stator and rotor heating into one model. <strong>Motor</strong> heating is reflected in<br />

the A1 STATUS MOTOR STATUS MOTOR THERMAL CAPACITY USED actual value register.<br />

If the motor has been stopped for a long period of time, it will be at ambient temperature<br />

5–38 <strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL