A: APPENDIX<br />

Once again, if the polarity of one of the phases is out by 180°, the magnitude of the<br />

resulting vector on a balanced system will be out by a factor of 1.73.<br />

On a three wire supply, this configuration will always work and unbalance will be detected<br />

properly. In the event of a single phase, there will always be a large unbalance present at<br />

the interposing CTs of the relay. If for example Phase A was lost, Phase A would read zero<br />

while Phase B and C would both read the magnitude of Phase C. If on the other hand,<br />

phase B was lost, at the supply, Phase A would be 180° out-of-phase with Phase C and the<br />

vector addition would equal zero at Phase B.<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL A–3