CHAPTER 1: <strong>GE</strong>TTING STARTED<br />

1.3.4 Enumeration Settings<br />

<br />

SETTINGS [<br />

Therefore, press the ENTER key to store the new value in memory.<br />

This flash message will momentarily appear as confirmation of the<br />

storing process.<br />

The example shown in the following figures illustrates the keypress sequences required to<br />

enter system parameters such as the phase CT primary rating, ground CT primary rating,<br />

bus VT connection type, secondary voltage, and VT ratio.<br />

The following values will be entered:<br />

Phase CT primary rating: 600 A<br />

<strong>Motor</strong> Full Load Current: 318 A<br />

Ground CT ratings: 50/5 A<br />

Phase Differential CT: None<br />

Voltage Transformer Connection Type: Open Delta<br />

<strong>Motor</strong> Nameplate Voltage: 13800 V<br />

VT Ratio: 115:1<br />

To set the phase CT primary rating, modify the S2 SYSTEM SETUP CURRENT SENSING <br />

PHASE CT PRIMARY settings as shown below.<br />

Press MESSA<strong>GE</strong> or ENTER<br />

<br />

SETTINGS [<br />

Press MESSA<strong>GE</strong> <br />

<br />

SETTINGS [<br />

Press<br />

MESSA<strong>GE</strong> <br />

or ENTER<br />

NEW SETTINGS<br />

HAS<br />

BEEN STORED<br />

Press the MENU key until the relay displays the Settings menu<br />

header.<br />

<br />

CURRENT [<br />

Press<br />

MESSA<strong>GE</strong> <br />

or ENTER<br />

PHASE CT PRIMARY:<br />

OFF<br />

Press the VALUE keys until 600 A is PHASE CT PRIMARY:<br />

displayed, or enter the value directly via 600 A<br />

the numeric keypad.<br />

Press the ENTER key to store the NEW SETTINGS<br />

settings. HAS<br />

To set the phase <strong>Motor</strong> Full Load Amps FLA, modify the S2 SYSTEM SETUP CURRENT<br />

SENSING MOTOR FULL LOAD AMPS FLA settings as shown below.<br />

Press the MENU key until the relay displays the Settings menu<br />

header.<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 1–11