CHAPTER 5: SETTINGS<br />

5.3 S2 System Setup<br />

Note<br />

Note<br />

5.3.1 Current Sensing<br />

PATH: SETTINGS S2 SYSTEM SETUP CURRENT SENSING<br />

<br />

CURRENT [<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

PHASE CT PRIMARY:<br />

Not Programmed<br />

MOTOR FULL LOAD<br />

AMPS<br />

GROUND CT:<br />

50:0.025<br />

GROUND CT PRI-<br />

MARY:<br />

PHASE DIFFEREN-<br />

TIAL<br />

PHASE DIFFEREN-<br />

TIAL<br />

ENABLE 2-SPEED<br />

MOTOR<br />

SPEED2 PHASE CT<br />

PRIMARY: 100 A<br />

SPEED2 MOTOR<br />

FLA: 1 A<br />

Range: 1 to 5000 A in steps of 1. Values<br />

≥5001 denote not<br />

Range: 1 to 5000 A in steps of 1. Values<br />

≥5001 denote not<br />

Range: None, 1A Secondary, 5A<br />

Secondary, 50:0.025<br />

Range: 1 to 5000 A in steps of 1<br />

Range: None, 1A Secondary, 5A<br />

Secondary<br />

Range: 1 to 5000 in steps of 1<br />

Range: No, Yes<br />

Range: 1 to 5000 A in steps of 1<br />

Range: 1 to 5000 A in steps of 1<br />

The GROUND CT PRIMARY and PHASE DIFFERENTIAL CT PRIMARY settings are seen only if<br />

the GROUND CT is set to “1A Secondary” or “5A Secondary”.<br />

The SPEED2 PHASE CT PRIMARY and SPEED2 MOTOR FLA settings are seen only if two-speed<br />

motor protection is enabled.<br />

As a safeguard, PHASE CT PRIMARY and MOTOR FULL LOAD AMPS are defaulted to “Not<br />

Programmed” when shipped. A block start indicates the <strong>469</strong> was never programmed. Once<br />

PHASE CT PRIMARY and MOTOR FULL LOAD AMPS are entered, the alarm resets itself. The<br />

phase CT should be chosen so the FLA is no less than 50% of the rated phase CT primary.<br />

Ideally, the phase CT primary should be chosen so the FLA is 100% of the phase CT primary<br />

or slightly less, never more. The secondary value of 1 or 5 A must be specified at the time of<br />

order so that the proper hardware is installed. A value for MOTOR FULL LOAD AMPS (FLA)<br />

must also be entered. The value may be taken from the motor nameplate data sheets. The<br />

service factor may be entered as overload pickup (see S5 Thermal Model on page 5–36).<br />

For high resistance grounded systems, sensitive ground current detection is possible if the<br />

50:0.025 ground CT input is used. To use the 50:0.025 input, select “50:0.025” for the<br />

GROUND CT settings. No additional ground CT messages will appear. On solidly grounded<br />

systems where fault currents may be quite large, the <strong>469</strong> 1A or 5A secondary ground CT<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 5–17