06.05.2013 Views

Multilin 469 Motor Management Relay ... - GE Digital Energy

Multilin 469 Motor Management Relay ... - GE Digital Energy

Multilin 469 Motor Management Relay ... - GE Digital Energy

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

• Short Circuit Trip<br />

CHAPTER 1: <strong>GE</strong>TTING STARTED<br />

The short circuit trip should be set above the maximum locked rotor current but below<br />

the short circuit current of the fuses. The data sheets indicate a maximum locked rotor<br />

current of 630% FLC or 6.3 × FLC. A setting of 7 × FLC with a instantaneous time delay<br />

will be ideal but nuisance tripping may result due to the asymmetrical starting<br />

currents and DC offset. If asymmetrical starting currents limits the starting capability,<br />

set the S/C level higher to a maximum of 11 × FLC to override this condition<br />

(1.7 × 6.3 = 11.7 where 1.7 is the maximum DC offset for an asymmetrical current).<br />

• Ground Fault<br />

Unfortunately, there is not enough information to determine a ground fault setting.<br />

These settings depend on the following information:<br />

1. The ground fault current available.<br />

2. System grounding; for example, high resistive grounding or solidly grounded<br />

3. Ground fault CT used.<br />

4. Ground fault connection; for example, zero-sequence or residual connection<br />

For the purpose of this example, assume a fault current of 10 Amps or 10/50 = 0.2 x<br />

CT, no intentional time delay.<br />

• Unbalance Alarm and Trip<br />

The unbalance settings are determined by examining the motor application and<br />

motor design. The heating effect of unbalance will be protected by enabling<br />

unbalance input to thermal memory; described in details in Chapter 5, Thermal Model.<br />

A setting of 10% for the unbalance alarm with a delay of 10 seconds would be<br />

appropriate and the trip can be set to 25% with a delay of 5 seconds.<br />

• Stopped and Running Cool Times<br />

The motor manufacturer usually supplies this information as either cooling times, or<br />

cooling time constants not provided in the data sheet issued with this motor. Since<br />

RTDs are present and wired to the relay, biasing of the thermal model will be used so it<br />

is not critical to have these cooling times from the manufacturer. The default values of<br />

motor cooling time constants are 15 and 30 minutes, and can be used for the running<br />

and stopped cool times respectively. If the manufacturer provides cooling times<br />

instead, the approximate values of the cooling time constants is 1/5th the cooling<br />

times provided by the manufacturer.<br />

• Acceleration Trip<br />

This settings should be set higher than the maximum starting time to avoid nuisance<br />

tripping when the voltage is lower or for varying loads during acceleration. If reduced<br />

voltage starting is used, according to the acceleration curves, a setting of 18 seconds<br />

would be appropriate, or if across the line starting is used, a setting of 13 seconds<br />

would be appropriate.<br />

• Enable Start Inhibit<br />

This function will limit starts when the motor is already hot. The relay learns the<br />

amount of thermal capacity used at start. If the motor is hot, thus having some<br />

thermal capacity used, the relay will not allow a start if the available thermal capacity<br />

is less than the required thermal capacity for a start.<br />

1–28 <strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!