A: APPENDIX<br />

• Programming the START INHIBIT settings to “On” makes a restart possible as soon<br />

as 62.5% (50 × 1.25) thermal capacity is available.<br />

• After two (2) cold or one (1) hot start, the thermal capacity used will approach<br />

100%. The thermal capacity used decays exponentially (see <strong>Motor</strong> Cooling on page<br />

5–55 for details). As such, the thermal capacity used after 1 time constant will be<br />

37%, meaning there is enough thermal capacity available for another start.<br />

Program 300 minutes (5 hours) as the COOL TIME CONSTANT STOPPED settings.<br />

Thus, after two (2) cold or one (1) hot start, a stopped motor will be blocked from<br />

starting for 5 hours.<br />

• Since the rotor cools faster when the motor is running, a reasonable setting for the<br />

running cool time constant might be half the stopped cool time constant or 150<br />

minutes.<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL A–5