06.05.2013 Views

Multilin 469 Motor Management Relay ... - GE Digital Energy

Multilin 469 Motor Management Relay ... - GE Digital Energy

Multilin 469 Motor Management Relay ... - GE Digital Energy

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

CHAPTER 5: SETTINGS<br />

input should be used for either zero-sequence or residual ground sensing. If the connection<br />

is residual, the Ground CT secondary and primary values should be the same as the phase<br />

CT. If however, the connection is zero-sequence, the Ground CT secondary and primary<br />

values must be entered. The Ground CT primary should be selected such that potential<br />

fault current does not exceed 20 times the primary rating. When relaying class CTs are<br />

purchased, this precaution will ensure that the Ground CT does not saturate under fault<br />

conditions.<br />

The PHASE DIFFERENTIAL CT PRIMARY must be entered if the differential feature is to be<br />

used. If two CTs are used per phase in a vectorial summation configuration, the CTs should<br />

be chosen to ensure there is no saturation during motor starting. If however, a core<br />

balance CT is used for the differential protection in each phase, a low CT rating of 50 or 100<br />

A allows for very sensitive differential protection.<br />

When the two-speed motor feature is used, a value for a second set of Phase CTs and<br />

motor FLA must be entered here for Speed 2. If the Phase CTs are the same as the speed 1<br />

phase CTs, simply enter the same value here as well.<br />

Example 1:<br />

Consider a <strong>469</strong> with a 5 A Phase CT secondary and Ground Fault Detection set to Residual<br />

and a motor with the following specifications:<br />

<strong>Motor</strong> Nameplate FLA: 87 A; Low Resistance Grounded; Maximum Fault: 400 A<br />

The following settings are required:<br />

PHASE CT PRIMARY: “100”<br />

MOTOR FULL LOAD AMPS: “87”<br />

GROUND CT: “5 A Secondary”<br />

GROUND CT PRIMARY: “100”<br />

Example 2:<br />

Consider a <strong>469</strong> with a 5 A Phase CT secondary and Ground Fault Detection set to Residual<br />

and a motor with the following specifications:<br />

<strong>Motor</strong> Nameplate FLA: 255 A; Solidly Grounded; Maximum Fault: 10000 A;<br />

Zero Sequence Ground CT: (10000/20) 500:1<br />

The following settings are required:<br />

PHASE CT PRIMARY: “300”<br />

MOTOR FULL LOAD AMPS: “255”<br />

GROUND CT: “5 A Secondary”<br />

GROUND CT PRIMARY: “500”<br />

Example 3:<br />

Again, consider a <strong>469</strong> with a 5 A Phase CT secondary and Ground Fault Detection set to<br />

Residual and a motor with the following specifications:<br />

<strong>Motor</strong> Nameplate FLA: 330 A; High Resistance Grounded; Maximum Fault: 5 A<br />

The following settings are required:<br />

5–18 <strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!