CHAPTER 5: SETTINGS<br />

This feature compares two of the analog inputs and activate alarms or trips based on the<br />

difference between them. The difference can be of an absolute difference in units or a<br />

percentage difference. The second analog input (4 for 3-4) is used as the reference value<br />

for percentage calculations. The comparison logic can also be selected as one input<br />

greater than the other (“3>4”) or vice versa (“4>3”) or as absolute difference (“34”). Note<br />

that the compared analog inputs must be programmed with the same unit type prior to<br />

using this feature.<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 5–97