Note<br />

3.2.11 Drawout Indicator<br />

FIGURE 3–26: Alternate Wiring for Contactors<br />

CHAPTER 3: INSTALLATION<br />

The Drawout Indicator is simply a jumper from terminals E12 to F12. When the <strong>469</strong> is<br />

withdrawn from the case, terminals E12 and F12 are open. This may be useful for<br />

differentiating between loss of control power as indicated by the 6 SERVICE relay and<br />

withdrawal of the unit.<br />

3.2.12 RS485 Communications Ports<br />

Two independent two-wire RS485 ports are provided. Up to 32 <strong>469</strong>s can be daisy-chained<br />

together on a communication channel without exceeding the driver capability. For larger<br />

systems, additional serial channels must be added. Commercially available repeaters can<br />

also be used to add more than 32 relays on a single channel. Suitable cable should have a<br />

characteristic impedance of 120 Ω (e.g. Belden #9841) and total wire length should not<br />

exceed 4000 ft. Commercially available repeaters will allow for transmission distances<br />

greater than 4000 ft.<br />

Voltage differences between remote ends of the communication link are not uncommon.<br />

For this reason, surge protection devices are internally installed across all RS485 terminals.<br />

Internally, an isolated power supply with an optocoupled data interface is used to prevent<br />

noise coupling.<br />

To ensure that all devices in a daisy-chain are at the same potential, it is imperative<br />

that the common terminals of each RS485 port are tied together and grounded only<br />

once, at the master. Failure to do so may result in intermittent or failed<br />

communications.<br />

3–24 <strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL