CHAPTER 6: ACTUAL VALUES<br />

6.4 A3 Learned Data<br />

6.4.1 <strong>Motor</strong> Starting<br />

PATH: ACTUAL VALUES A3 LEARNED DATA MOTOR STARTING<br />

<br />

MOTOR [<br />

]<br />

STARTING<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

LEARNED ACCELERA-<br />

TION<br />

TIME: 0.0 s<br />

LEARNED STARTING<br />

CURRENT: 0 A<br />

LEARNED STARTING<br />

CAPACITY: 0% used<br />

LAST ACCELERATION<br />

TIME: 0.0 s<br />

LAST STARTING<br />

CURRENT: 0 A<br />

LAST STARTING<br />

CAPACITY: 0% used<br />

Range: 0.0 to 200.0 sec.<br />

Range: 0 to 50000 A<br />

Range: 0 to 100%<br />

Range: 0.0 to 200.0 sec.<br />

Range: 0 to 50000 A<br />

Range: 0 to 100%<br />

The <strong>469</strong> learns the acceleration time, the starting current, as well as, the thermal capacity<br />

required during motor starts. This data is accumulated based on the last five starts. The<br />

<strong>469</strong> also keeps statistics for last acceleration time, last starting current, and last starting<br />

capacity. This information can be reset to default using the S1 <strong>469</strong> SETUP INSTALLATION<br />

RESET MOTOR INFORMATION settings.<br />

If motor load during starting is relatively consistent, the LEARNED ACCELERATION TIME<br />

may be used to fine tune the acceleration protection. Learned acceleration time will be the<br />

longest time of the last five successful starts. The time is measured from the transition of<br />

motor current from zero to greater than overload pickup, until line current falls below the<br />

overload pickup level.<br />

LEARNED STARTING CURRENT is measured 200 ms after the transition of motor current<br />

from zero to greater than overload pickup. This should ensure that the measured current is<br />

symmetrical. The value displayed is the average of the last 5 successful starts. If there are<br />

less than 5 starts, 0s will be averaged in for the full 5 starts.<br />

The LEARNED STARTING CAPACITY is used to determine if there is enough thermal capacity<br />

to permit a start (refer to Start Inhibit on page 5–66 for more information on start inhibit). If<br />

there is not enough thermal capacity for a start, a start inhibit will be issued. Starting will<br />

be blocked until there is sufficient thermal capacity.<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 6–27