5.5 S4 Output <strong>Relay</strong>s<br />

5.5.1 Description<br />

5.5.2 <strong>Relay</strong> Reset Mode<br />

CHAPTER 5: SETTINGS<br />

Five of the six output relays are always non-failsafe; the 6 SERVICE relay is always failsafe.<br />

As failsafe, the 6 SERVICE relay will be energized normally and de-energize when called<br />

upon to operate. It will also de-energize when control power to the <strong>469</strong> is lost and<br />

therefore, be in its operated state. All other relays, being non-failsafe, will be de-energized<br />

normally and energize when called upon to operate. Obviously, when control power is lost<br />

to the <strong>469</strong>, the output relays must be de-energized and therefore, they will be in their nonoperated<br />

state. Shorting bars in the drawout case ensure that when the <strong>469</strong> is drawn out,<br />

no trip or alarm occurs. The the 6 SERVICE relay will however indicate that the <strong>469</strong> has<br />

been drawn out.<br />

PATH: SETTINGS S4 OUTPUT RELAYS RELAY RESET MODE<br />

<br />

RELAY [<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

1 TRIP:<br />

All Resets<br />

2 AUXILIARY:<br />

All Resets<br />

3 AUXILIARY:<br />

All Resets<br />

4 ALARM:<br />

All Resets<br />

5 BLOCK START:<br />

Auto-Reset<br />

6 SERVICE:<br />

All Resets<br />

Range: All Resets, Remote Reset Only,<br />

Keypad Reset Only<br />

Range: All Resets, Remote Reset Only,<br />

Keypad Reset Only<br />

Range: All Resets, Remote Reset Only,<br />

Keypad Reset Only<br />

Range: All Resets, Remote Reset Only,<br />

Keypad Reset Only<br />

Range: N/A<br />

Range: All Resets, Remote Reset Only,<br />

Keypad Reset Only<br />

A latched trip or alarm may be reset at any time, providing that the condition that caused<br />

the trip or alarm is no longer present. Unlatched trips and alarms will reset automatically<br />

once the condition is no longer present. If any condition may be reset, the Reset Possible<br />

LED will be lit. All Block Start features reset automatically when the lockout time has<br />

expired and the trip has been reset.<br />

The other relays may be programmed to All Resets which allows reset from the front<br />

keypad or the remote reset switch input or the communications port. Optionally, relays 1<br />

through 6 may be programmed to reset by the “Remote Reset Only” (by the remote reset<br />

switch input or the communications port) or “Keypad Reset Only” (reset only by relay<br />

keypad).<br />

NO trip or alarm element must EVER be assigned to two output relays where one is<br />

Remote Reset Only and the other is Keypad Reset Only. The trip or alarm will not be<br />

resettable if this occurs.<br />

5–34 <strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL