General Switch A to D<br />

PATH: SETTINGS S3 DIGITAL INPUTS ASSIGNABLE INPUT 1(4)<br />

<br />

ASSIGNABLE [<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

CHAPTER 5: SETTINGS<br />

These settings apply only if the INPUT 1(4) FUNCTION is “General Switch A”. Similar messages<br />

appear for General Switches B, C, and D.<br />

There are four general switch functions assignable to the four digital inputs. Once a<br />

general switch function is chosen for one of the digital inputs, the settings messages<br />

shown here follow the assignment message. An alarm and/or trip may then be configured<br />

for that input. The alarm and/or trip may be assigned a common name and a common<br />

block time from motor start if required (if the alarm is to be disabled until some period of<br />

time after he motor has been started). A value of “0” for the BLOCK TIME settings indicates<br />

that the feature is always active, when the motor is stopped or running. The switch may<br />

also be defined as normally open or normally closed. After the block delay has expired, the<br />

digital input will be monitored. If the switch is not in its normal state after the specified<br />

delay, an alarm or trip will occur.<br />

Capture Trace<br />

INPUT 1 FUNCTION:<br />

General Sw. A<br />

SWITCH NAME:<br />

General Sw. A<br />

<strong>GE</strong>NERAL SWITCH A:<br />

Normally Open<br />

BLOCK INPUT<br />

FROM START: 0 s<br />

<strong>GE</strong>NERAL SWITCH A<br />

ALARM: Off<br />

ASSIGN ALARM<br />

RELAYS:<br />

Range: See above<br />

PATH: SETTINGS S3 DIGITAL INPUTS ASSIGNABLE INPUT 1(4)<br />

<br />

ASSIGNABLE [<br />

<strong>GE</strong>NERAL SWITCH A<br />

ALARM DELAY: 5.0<br />

<strong>GE</strong>NERAL SWITCH A<br />

EVENTS: Off<br />

<strong>GE</strong>NERAL SWITCH A<br />

TRIP: Off<br />

ASSIGN TRIP<br />

RELAYS:<br />

<strong>GE</strong>NERAL SWITCH A<br />

TRIP DELAY: 5.0 s<br />

INPUT 1 FUNCTION:<br />

Capture Trace<br />

Range: 12 alphanumeric characters<br />

Range: Normally Open,<br />

Normally Closed.<br />

Range: 0 to 5000 s in steps of 1<br />

Range: Off, Latched, Unlatched<br />

Range: Alarm, Alarm & Auxiliary2,<br />

Alarm & Aux2 & Aux3, Alarm &<br />

Auxiliary3, Auxiliary2, Aux2 &<br />

Aux3, Auxiliary3, None<br />

Range: 0.1 to 5000.0 s in steps of 0.1<br />

Range: On, Off<br />

Range: Off, Latched, Unlatched<br />

Range: Trip, Trip & Auxiliary2, Trip &<br />

Aux2 & Aux3, Trip & Auxiliary3<br />

Range: 0.1 to 5000.0 s in steps of 0.1<br />

Range: See above.<br />

5–32 <strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL