CHAPTER 5: SETTINGS<br />

5.13 S12 Analog Inputs/Outputs<br />

5.13.1 Analog Outputs 1 to 4<br />

PATH: SETTINGS S12 ANALOG I/O ANALOG OUTPUT 1<br />

<br />

ANALOG [<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

<br />

ANALOG [<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

<br />

ANALOG [<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

<br />

ANALOG [<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

ANALOG OUTPUT 1:<br />

Therm. Capacity<br />

THERM. CAPACITY<br />

USED<br />

THERM. CAPACITY<br />

USED<br />

ANALOG OUTPUT 2:<br />

<strong>Motor</strong> Load<br />

MOTOR LOAD<br />

MIN: 0.00 x FLA<br />

MOTOR LOAD<br />

MAX: 1.50 x FLA<br />

ANALOG OUTPUT 3:<br />

Hottest Stator<br />

HOTTEST STATOR<br />

RTD<br />

HOTTEST STATOR<br />

RTD<br />

ANALOG OUTPUT 4:<br />

Real Power (kW)<br />

REAL POWER (kW)<br />

MIN: 0 kW<br />

REAL POWER (kW)<br />

MAX: 1000 kW<br />

Range: See Analog Output Parameter<br />

Selection Table on page 5–92<br />

Range: 0 to 100% in steps of 1<br />

Range: 0 to 100% in steps of 1<br />

Range: See Analog Output Parameter<br />

Selection Table on page 5–92<br />

Range: 0.00 to 20.00 x FLA in steps of<br />

0.01<br />

Range: 0.00 to 20.00 x FLA in steps of<br />

0.01<br />

Range: See Analog Output Parameter<br />

Selection Table on page 5–92<br />

Range: –50 to 250°C (or –58 to 482°F)<br />

in steps of 1<br />

Range: –50 to 250°C (or –58 to 482°F)<br />

in steps of 1<br />

Range: See Analog Output Parameter<br />

Selection Table on page 5–92<br />

Range: –50000 to 50000 kW in steps of<br />

1<br />

Range: –50000 to 50000 kW in steps of<br />

1<br />

The <strong>469</strong> has four analog output channels (4 to 20 mA or 0 to 1 mA as ordered). Each<br />

channel may be individually configured to represent a number of different measured<br />

parameters as shown in the table below. The minimum value programmed represents the<br />

4 mA output. The maximum value programmed represents the 20 mA output. If the<br />

maximum is programmed lower than the minimum, the output will function in reverse. All<br />

four of the outputs are updated once every 50 ms. Each parameter may only be used<br />

once.<br />

For example, the analog output parameter may be chosen as “Hottest Stator RTD” for a 4<br />

to 20 mA output. If the minimum is set for “0°C” and the maximum is set for “250°C”, the<br />

analog output channel will output 4 mA when the Hottest Stator RTD temperature is at 0°C,<br />

12 mA when it is 125°C, and 20 mA when it is 250°C.<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 5–91