CHAPTER 5: SETTINGS<br />

5.2.4 Real Time Clock<br />

PATH: SETTINGS S1 <strong>469</strong> SETUP REAL TIME CLOCK<br />

REAL<br />

TIME []<br />

5.2.5 Default Messages<br />

MESSA<strong>GE</strong><br />

The correct time and date must be entered for event recorder events to be correctly time/<br />

date stamped. A supercap backed internal clock runs for 45 days even when power is off. It<br />

has an accuracy of approximately ±5 minutes per month. It must be periodically corrected<br />

manually through the front panel or via the RS485 serial link clock update command. If the<br />

approximate time an event occurred without synchronization to other relays is sufficient,<br />

then entry of time/date from the front panel keys is adequate.<br />

If the RS485 serial communication link is used, then all the relays can keep synchronized<br />

time. A new clock time is pre-loaded into the <strong>469</strong> memory via the RS485 port by a remote<br />

computer to each relay connected on the communications channel. After the computer<br />

broadcasts (address 0) a “set clock” command, all relays in the system begin timing at the<br />

same instant. There can be up to 100 ms of delay in receiving serial commands so the<br />

clock time in each relay is ±100 ms, ± the absolute clock accuracy in the PLC or PC. Refer to<br />

<strong>GE</strong> publication <strong>GE</strong>K-106491: <strong>469</strong> Communications Guide for information on programming<br />

the time preload and synchronizing commands.<br />

PATH: SETTINGS S1 <strong>469</strong> SETUP DEFAULT MESSA<strong>GE</strong>S<br />

<br />

DEFAULT [<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

DATE (MM.DD.YYYY)<br />

01/01/1994<br />

TIME (HH.MM.SS):<br />

12:00:00<br />

DEFAULT MESSA<strong>GE</strong>S<br />

6 OF 20 ASSIGNED<br />

MOTOR STATUS:<br />

Stopped<br />

A: 0 B:<br />

0<br />

MOTOR LOAD:<br />

0.00 x FLA<br />

CURRENT UNBAL-<br />

ANCE:<br />

DATE: 01/01/1995<br />

TIME: 12:00:00<br />

MULTILIN <strong>469</strong><br />

<strong>Motor</strong><br />

Range: 01 to 12 / 01 to 31 / 1995 to<br />

2094<br />

Range: 00 to 23 hrs / 00 to 59 min. / 00<br />

to 59 sec.<br />

Range: N/A<br />

Range: N/A<br />

Range: N/A<br />

Range: N/A<br />

Range: N/A<br />

Range: N/A<br />

Range: N/A<br />

After a period of inactivity, the <strong>469</strong> displays default messages. Between 1 and 20 default<br />

messages can be selected. Multiple default messages sequentially scan at a rate<br />

determined by the S1 <strong>469</strong> SETUP PREFERENCES DEFAULT MESSA<strong>GE</strong> CYCLE TIME settings.<br />

Any actual value can be selected for default display. In addition, up to five user<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 5–13