CHAPTER 5: SETTINGS<br />

There are 4 analog inputs, 4 to 20 mA, 0 to 20 mA, or 0 to 1 mA as selected. These inputs<br />

may be used to monitor transducers such as vibration monitors, tachometers, pressure<br />

transducers, etc. These inputs may be used for alarm and tripping purposes. The inputs are<br />

sampled every 50 ms. The level of the analog input is also available over the<br />

communications port.<br />

Before the input may be used, it must be configured. A name may be assigned for the<br />

input, units may be assigned, and a minimum and maximum value may be assigned. Also,<br />

the trip and alarm features may be blocked from start for a specified time delay. If the<br />

block time is 0, there is no block and the trip and alarm features will be active when the<br />

motor is stopped or running. If a time is programmed other than 0, the feature will be<br />

disabled when the motor is stopped and also from the time a start is detected until the<br />

time entered expires. Once the input is setup, both the trip and alarm features may be<br />

configured. In addition to programming a level and time delay, the pickup settings may be<br />

used to dictate whether the feature picks up when the measured value is over or under the<br />

level.<br />

For example, if a pressure transducer is to be used for a pump application, program the<br />

following settings:<br />

ANALOG INPUT 1(4) NAME: “Pressure”<br />

ANALOG INPUT 1(4) UNITS: “PSI”<br />

ANALOG INPUT 1(4) MINIMUM: “0”<br />

ANALOG INPUT 1(4) MAXIMUM: “500”<br />

If there is no pressure until the pump is up and running for 5 minutes and pressure builds<br />

up, program the ANALOG INPUT 1 BLOCK FROM START as 6 minutes (“360 s”). The alarm may<br />

be fed back to a PLC for when pressure is under 300 PSI. Program a reasonable delay (e.g<br />

ANALOG INPUT ALARM 1 DELAY =“3s”) and ANALOG INPUT ALARM 1 PICKUP as “Under”.<br />

If a vibration transducer is to be used for a pump application, program the following<br />

settings:<br />

ANALOG INPUT 1(4) NAME: “Vibration”<br />

ANALOG INPUT 1(4) UNITS: “mm/s”<br />

ANALOG INPUT 1(4) MINIMUM: “0”<br />

ANALOG INPUT 1(4) MAXIMUM: “25”<br />

Range: –50000 to 50000 in steps of 1<br />

Units reflect ANALOG INPUT 1<br />

UNITS above<br />

Range: Over, Under<br />

Range: 0.1 to 300.0 s in steps of 0.1<br />

Program BLOCK ANALOG INPUT 1(4) FROM START as “0” minutes. Set the alarm for a<br />

reasonable level slightly higher than the normal vibration level. Program a delay of “3 s”<br />

and a pickup value of “Over”.<br />

5–94 <strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL