CHAPTER 3: INSTALLATION<br />

3.2.5 Voltage Inputs<br />

FIGURE 3–18: Summation Method with Phase CTs<br />

FIGURE 3–19: Summation Method without Phase CTs<br />

The <strong>469</strong> has three channels for AC voltage inputs, each with an isolating transformer. There<br />

are no internal fuses or ground connections on the voltage inputs. The maximum VT ratio is<br />

300.00:1. The two VT connections are open delta (see FIGURE 3–12: Typical Wiring Diagram<br />

on page 3–11) or wye (see below). The voltage channels are connected in wye internally,<br />

which means that the jumper shown on the delta-source connection of the typical wiring<br />

diagram, between the phase B input and the <strong>469</strong> neutral terminal, must be installed for<br />

open delta VTs.<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 3–17