5.7.2 Overload Alarm<br />

be increased if nuisance tripping occurs.<br />

CHAPTER 5: SETTINGS<br />

When a motor starts, the starting current (typically 6 × FLA for an induction motor) has an<br />

asymmetrical component. This asymmetrical current may cause one phase to see as<br />

much as 1.6 times the normal RMS starting current. If the SHORT CIRCUIT TRIP PICKUP was<br />

set at 1.25 times the symmetrical starting current, it is probable that there would be<br />

nuisance trips during motor starting. A rule of thumb has been developed over time that<br />

short circuit protection at least 1.6 times the symmetrical starting current value. This<br />

allows the motor to start without nuisance tripping.<br />

The overreach filter removes the DC component from the asymmetrical current present at<br />

the moment of fault. This eliminates overreach; however, the response time slows slightly<br />

(10 to 15 ms) but remains within specification.<br />

PATH: SETTINGS S6 CURRENT ELEM. OVERLOAD ALARM<br />

<br />

OVERLOAD [<br />

5.7.3 Mechanical Jam<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

OVERLOAD<br />

ALARM: Off<br />

ASSIGN ALARM<br />

RELAYS:<br />

If enabled as “Latched” or “Unlatched”, the Overload Alarm functions as follows. After a<br />

motor start, when the equivalent motor heating current exceeds the OVERLOAD PICKUP<br />

LEVEL, an alarm will occur. If programmed as “Unlatched”, the overload alarm resets itself<br />

when the motor is no longer in overload. If programmed as “Latched”, the RESET key must<br />

be pressed to reset the alarm once the overload condition is gone. Event recording for all<br />

alarm features is optional.<br />

For example, it may be desirable to have an unlatched alarm connected to a PLC that is<br />

controlling the load on a motor.<br />

PATH: SETTINGS S6 CURRENT ELEM. MECHANICAL JAM<br />

<br />

MECHANICAL [<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

OVERLOAD ALARM<br />

DELAY: 0.1 s<br />

OVERLOAD ALARM<br />

EVENTS: Off<br />

MECHANICAL JAM<br />

TRIP: Off<br />

ASSIGN TRIP<br />

RELAYS:<br />

MECHANICAL JAM<br />

PICKUP: 1.50 x<br />

MECHANICAL JAM<br />

DELAY: 1 s<br />

Range: Off, Latched, Unlatched<br />

Range: Alarm, Auxiliary2, Auxiliary3,<br />

Alarm & Aux2, Alarm & Aux3,<br />

Aux2 & Aux3, Alarm & Aux2 &<br />

Aux3, None<br />

Range: 0.1 to 60 s in steps of 0.1<br />

Range: On, Off<br />

Range: Off, Latched, Unlatched<br />

Range: Trip, Trip & Auxiliary2, Trip &<br />

Aux2 & Aux3, Trip & Auxiliary3<br />

Range: 1.01 to 3.00 x FLA in steps of<br />

0.01<br />

Range: 1 to 30 s in steps of 1<br />

5–60 <strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL