CHAPTER 5: SETTINGS<br />

5.14.4 Test Output <strong>Relay</strong>s<br />

PATH: SETTINGS S13 <strong>469</strong> TESTING TEST OUTPUT RELAYS<br />

<br />

TEST [<br />

5.14.5 Test Analog Outputs<br />

In addition to the simulation modes, the TEST OUTPUT RELAYS settings group may be used<br />

during startup or testing to verify that the output relays are functioning correctly.<br />

The output relays can only be forced to operate only if the motor is stopped and there are<br />

no trips, alarms, or start blocks active. If any relay is forced to operate, the relay will toggle<br />

from its normal state when there are no trips, alarms, or blocks to its active state. The<br />

appropriate relay indicator will illuminate at that time. Selecting “Disabled” places the<br />

output relays back in service. If the <strong>469</strong> measures phase current or control power is cycled,<br />

the FORCE OPERATION OF RELAYS settings will automatically become disabled and the<br />

output relays will revert back to their normal states.<br />

If any relay is forced, the <strong>469</strong> In Service LED will flash, indicating that the <strong>469</strong> is not in<br />

protection mode.<br />

PATH: SETTINGS S13 <strong>469</strong> TESTING TEST ANALOG OUTPUT<br />

<br />

TEST [<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

FORCE OPERATION<br />

OF<br />

FORCE ANALOG OUT-<br />

PUTS<br />

ANALOG OUTPUT 1<br />

FORCED VALUE: 0%<br />

ANALOG OUTPUT 2<br />

FORCED VALUE: 0%<br />

ANALOG OUTPUT 3<br />

FORCED VALUE: 0%<br />

ANALOG OUTPUT 4<br />

FORCED VALUE: 0%<br />

Range: Disabled, 1 Trip, 2 Auxiliary,<br />

3 Auxiliary, 4 Alarm, 5 Block,<br />

6 Service, All <strong>Relay</strong>s, No <strong>Relay</strong>s<br />

Range: Enabled, Disabled<br />

Range: 0 to 100%, step 1<br />

Range: 0 to 100%, step 1<br />

Range: 0 to 100%, step 1<br />

Range: 0 to 100%, step 1<br />

In addition to the simulation modes, the TEST ANALOG OUTPUT settings group may be used<br />

during startup or testing to verify that the analog outputs are functioning correctly.<br />

The analog outputs can only be forced if the motor is stopped and there are no trips,<br />

alarms, or start blocks active. When the FORCE ANALOG OUTPUTS FUNCTION is “Enabled”,<br />

the output reflects the forced value as a percentage of the 4 to 20 mA or 0 to 1 mA range.<br />

Selecting “Disabled” places all four analog output channels back in service, reflecting the<br />

parameters programmed to each. If the <strong>469</strong> measures phase current or control power is<br />

cycled, the FORCE ANALOG OUTPUTS FUNCTION is automatically disabled and all analog<br />

outputs revert back to their normal state.<br />

Any time the analog outputs are forced, the <strong>469</strong> In Service LED will flash, indicating that the<br />

<strong>469</strong> is not in protection mode.<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 5–101