CHAPTER 6: ACTUAL VALUES<br />

6.2.4 Alarm Status<br />

PATH: ACTUAL VALUES A1 STATUS ALARM STATUS<br />

ALARM<br />

STATUS []<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

NO ALARMS<br />

REMOTE ALARM<br />

STATUS: Active<br />

PRESSURE SWITCH<br />

ALARM STATUS:<br />

VIBRATION SWITCH<br />

ALARM STATUS:<br />

DIG. COUNTER<br />

ALARM:<br />

TACHOMETER<br />

ALARM: 3000 RPM<br />

<strong>GE</strong>NERAL SW. A<br />

ALARM STATUS:<br />

THERMAL CAPACITY<br />

ALARM: 100% USED<br />

XX.XX x FLA OVER-<br />

LOAD<br />

UNDERCURRENT<br />

ALARM<br />

CURRENT UNBALANCE<br />

ALARM: 15%<br />

GROUND FAULT<br />

ALARM: 25.3 A<br />

STATOR RTD #1<br />

ALARM: 135°C<br />

OPEN SENSOR<br />

ALARM:<br />

SHORT/LOW TEMP<br />

ALARM<br />

UNDERVOLTA<strong>GE</strong><br />

ALARM<br />

OVERVOLTA<strong>GE</strong> ALARM<br />

Vab= 4992 V 120%<br />

SYSTEM FREQUENCY<br />

ALARM: 59.4 Hz<br />

POWER FACTOR<br />

ALARM PF: 0.00<br />

Range: N/A. Message seen when no<br />

alarms are active<br />

Range: Active, Latched<br />

Range: Active, Latched<br />

Range: Active, Latched<br />

Range: 1 to 9999999999. Displays<br />

current value of digital counter<br />

Range: 0 to 3600 RPM. Displays current<br />

Tachometer <strong>Digital</strong> Input value<br />

Range: Active, Latched<br />

Range: 1 to 100. Thermal Capacity<br />

Used value is shown here<br />

Range: 0 to 99999 s. Shows overload<br />

level and estimated time to trip.<br />

Range: 1 to 5000 A; 5 to 99% FLA.<br />

Lowest phase current shown.<br />

Range: 0 to 100%. Reflects the present<br />

unbalance level<br />

Range: 0.1 to 5000 A. Reflects the<br />

present ground current level<br />

Range: –50 to 250°C<br />

Range: RTD with the open sensor as<br />

programmed for RTDs 1 to 12<br />

Range: 1 to 12. Shows RTD with the<br />

short/low temperature alarm<br />

Range: 0 to 20000 V; 50 to 99% of<br />

Rated<br />

Range: 0 to 20000 V; 101 to 150% of<br />

Rated<br />

Range: 0.00, 20.00 to 120.00 Hz<br />

Range: 0.00 to 0.99 Lead or Lag, 0.00,<br />

1.00<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 6–7