CHAPTER 4: INTERFACES<br />

4.3.4 Connecting to the <strong>Relay</strong><br />

Select “Ethernet” from the Interface drop-down list.<br />

This will display a number of interface parameters that must be<br />

entered for proper Ethernet functionality.<br />

Enter the IP address assigned to the relay.<br />

Enter the slave address and Modbus port values (from the S1 <strong>469</strong><br />

SETUP SERIAL PORTS menu) in the Slave Address and Modbus<br />

Port fields. Refer to <strong>GE</strong>K-106491C: <strong>469</strong> Communications Guide.<br />

Click the Read Order Code button to connect to the <strong>469</strong> device and<br />

upload the order code.<br />

If a communications error occurs, ensure that the <strong>469</strong> Ethernet<br />

communications values entered in the previous step correspond to<br />

the relay setting values.<br />

Click OK when the relay order code has been received.<br />

The new device will be added to the Site List window (or Online<br />

window) located in the top left corner of the main EnerVista <strong>469</strong><br />

Setup window.<br />

The <strong>469</strong> Site Device has now been configured for Ethernet communications. Proceed to the<br />

following section to begin communications.<br />

Now that the communications parameters have been properly configured, the user can<br />

easily connect to the relay.<br />

Expand the Site list by double clicking on the site name or clicking on<br />

the «+» box to list the available devices for the given site (for<br />

example, in the “Pumping Station 1” site shown below).<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 4–19