CHAPTER 5: SETTINGS<br />

Note<br />

5.5.3 Force Output <strong>Relay</strong><br />

For example, serious trips such as Short Circuit and Ground Fault may be assigned to the<br />

2 AUXILIARY relay so that they can only be reset via the remote reset terminals (D18 and<br />

D23) or the communication port. The remote reset terminals should be connected to a<br />

keyswitch so that only authorized personnel could reset such a critical trip.<br />

• Assign only Short Circuit and Ground Fault to the 2 AUXILIARY relay<br />

• Program 2 AUXILIARY to “Remote Reset Only”<br />

PATH: SETTINGS S4 OUTPUT RELAYS FORCE OUTPUT RELAYS<br />

<br />

FORCE [<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

FORCE 1 TRIP<br />

RELAY: Disabled<br />

FORCE TRIP RELAY<br />

DURATION: Static<br />

FORCE 2 AUXILIARY<br />

RELAY: Disabled<br />

FORCE 2 AUX RELAY<br />

DURATION: Static<br />

FORCE 3 AUXILIARY<br />

RELAY: Disabled<br />

FORCE 3 AUX RELAY<br />

DURATION: Static<br />

FORCE 4 ALARM<br />

RELAY: Disabled<br />

FORCE ALARM RELAY<br />

DURATION: Static<br />

FORCE 5 BLOCK<br />

START<br />

FORCE BLOCK RELAY<br />

DURATION: Static<br />

The output relays can be independently forced in static or dynamic mode. In static mode<br />

the selected relay will operate as long as it is in the “Enabled” state. Only when the user<br />

enters “Disabled” will the selected relay reset. In dynamic mode the user specifies the<br />

operate time (1 to 300 seconds) and the selected relay will operate for the specified<br />

duration.<br />

The FORCE OUTPUT RELAY option is NOT allowed when the selected relay output is already<br />

active due to trip or alarm condition, when the <strong>469</strong> is in start block condition, or when the<br />

<strong>469</strong> is not in service.<br />

IMPORTANT NOTE: The forced relay will override any trip or alarm conditions. (i.e. when the<br />

relay is forced and trip occurs, the relay will still be enabled when the trip condition is reset).<br />

Control power loss in the <strong>469</strong> will reset all forced relays.<br />

Range: Disabled, Enabled<br />

Range: Static, 1 to 300 s in steps of 1<br />

Range: Disabled, Enabled<br />

Range: Static, 1 to 300 s in steps of 1<br />

Range: Disabled, Enabled<br />

Range: Static, 1 to 300 s in steps of 1<br />

Range: Disabled, Enabled<br />

Range: Static, 1 to 300 s in steps of 1<br />

Range: Disabled, Enabled<br />

Range: Static, 1 to 300 s in steps of 1<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 5–35