06.05.2013 Views

Multilin 469 Motor Management Relay ... - GE Digital Energy

Multilin 469 Motor Management Relay ... - GE Digital Energy

Multilin 469 Motor Management Relay ... - GE Digital Energy

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Note<br />

7.2.8 Output <strong>Relay</strong>s<br />

FORCE<br />

OPERATION<br />

SETTINGS<br />

To verify the functionality of the output relays, perform the following steps:<br />

Using the settings:<br />

CHAPTER 7: TESTING<br />

S13 TESTING TEST OUTPUT RELAYS FORCE OPERATION OF RELAYS: “1 Trip”<br />

Select and store values as per the table below, verifying operation<br />

EXPECTED MEASUREMENT<br />

4 FOR SHORT<br />

ACTUAL MEASUREMENT<br />

4 FOR SHORT<br />

1 2 3 4 5 6 1 2 3 4 5 6<br />

no nc no nc no nc no nc no nc no nc no nc no nc no nc no nc no nc no nc<br />

1TRIP 4 4 4 4 4 4<br />

2AUXILIARY 4 4 4 4 4 4<br />

3AUXILIARY 4 4 4 4 4 4<br />

4ALARM 4 4 4 4 4 4<br />

5BLOCKSTART 4 4 4 4 4 4<br />

6 SERVICE 4 4 4 4 4 4<br />

All <strong>Relay</strong>s 4 4 4 4 4 4<br />

No <strong>Relay</strong>s 4 4 4 4 4 4<br />

The 6 SERVICE relay is failsafe or energized normally. Operating the 6 SERVICE relay causes<br />

it to de-energize.<br />