CHAPTER 7: TESTING<br />

7.2.4 <strong>GE</strong> <strong>Multilin</strong> 50:0.025 Ground Accuracy Test<br />

7.2.5 RTD Accuracy Test<br />

INJECTED<br />

CURRENT<br />

1 A UNIT<br />

A2 METERING DATA CURRENT METERING:<br />

EXPECTED<br />

CURRENT<br />

READING<br />

0.1 A 100 A<br />

0.2 A 200 A<br />

0.5 A 500 A<br />

1.0 A 1000 A<br />

The <strong>469</strong> specification for <strong>GE</strong> <strong>Multilin</strong> 50:0.025 ground current input accuracy is ±0.5% of CT<br />

rated primary (25 A). Perform the steps below to verify accuracy.<br />

Alter the following settings:<br />

S2 SYSTEM SETUP CURRENT SENSING GROUND CT: “50:0.025”<br />

Measured values should be ±0.125 A.<br />

PRIMARY<br />

INJECTED<br />

CURRENT<br />

MEASURED<br />

GROUND<br />

CURRENT<br />

Inject the values shown in the table below either as primary values<br />

into a <strong>GE</strong> <strong>Multilin</strong> 50:0.025 Core Balance CT or as secondary values<br />

that simulate the core balance CT.<br />

Verify accuracy of the measured values.<br />

View the measured values in:<br />

A2 METERING DATA CURRENT METERING<br />

SECONDARY<br />

INJECTED<br />

CURRENT<br />

0.25 A 0.125 mA 0.25 A<br />

1 A 0.5 mA 1.00 A<br />

10 A 5 mA 10.00 A<br />

25 A 12.5 mA 25.00 A<br />

The <strong>469</strong> specification for RTD input accuracy is ±2°. Perform the steps below.<br />

Alter the following settings:<br />

S8 RTD TEMPERATURE RTD TYPES STATOR RTD TYPE: “100 Ohm Platinum” (select<br />

desired type)<br />

S8 RTD TEMPERATURE RTD #1 RTD #1 APPLICATION: “Stator” (repeat for RTDs 2 to<br />

12)<br />

Measured values should be ±2°C or ±4°F.<br />

Alter the resistances applied to the RTD inputs as per the table below<br />

to simulate RTDs.<br />

Verify accuracy of the measured values.<br />

View measured values in:<br />

MEASURED DIFFERENTIAL<br />

CURRENT<br />

PHASE A PHASE B PHASE C<br />

EXPECTED<br />

CURRENT<br />

READING<br />

MEASURED<br />

GROUND<br />

CURRENT<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 7–5