Differential Current Inputs<br />

CHAPTER 3: INSTALLATION<br />

The <strong>469</strong> has three channels for differential current inputs, each with an isolating<br />

transformer. There are no internal ground connections on the current inputs. Each<br />

differential CT circuit is shorted by automatic mechanisms on the <strong>469</strong> case if the unit is<br />

withdrawn. The maximum differential CT primary current is 5000 A.<br />

The <strong>469</strong> measures up to 5 A secondary current for the differential CT inputs. Since the<br />

conversion range is relatively small, the 1 A or 5 A option is field programmable. Proper<br />

selection of this settings ensures proper reading of primary phase differential current. The<br />

1 A / 5 A differential CT chosen must be capable of driving the <strong>469</strong> differential CT burden<br />

(see Specifications on page 2–6 for ratings).<br />

The differential CTs may be core balance as shown in the first figure below. Alternatively,<br />

the summation of two CTs per phase into the differential input will provide a larger zone of<br />

protection. If the summation of two CTs is used, observation of CT polarity is important. The<br />

summation method may also be implemented using the phase CTs as shown below. They<br />

will have to have the same CT ratio.<br />

FIGURE 3–17: Core Balance Method<br />

3–16 <strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL