t τ<br />

TCused ( TCused_start – TCused_end) e ⁄ –<br />

=<br />

( ) + TCused_end TC used_end<br />

CHAPTER 5: SETTINGS<br />

where: TCused = thermal capacity used<br />

TCused_start = TCused value caused by overload condition<br />

TCused_end = TCused value dictated by the hot/cold safe stall ratio when<br />

the motor is running (= 0 when the motor is stopped)<br />

t = time in minutes<br />

τ = Cool Time Constant (running or stopped)<br />

Ieq = equivalent motor heating current<br />

ol_pkp = overload pickup settings as a multiple of FLA<br />

hot / cold = hot/cold safe stall ratio<br />

Thermal Capacity Used<br />

Thermal Capacity Used<br />

100<br />

75<br />

50<br />

25<br />

0<br />

0 30 60 90 120 150 180<br />

Time in Minutes<br />

100<br />

75<br />

50<br />

25<br />

Cool Time Constant= 15min<br />

TCused_start= 85%<br />

Hot/Cold Ratio= 80%<br />

Ieq/Overload Pickup= 80%<br />

80% LOAD<br />

Cool Time Constant= 30min<br />

TCused_start= 85%<br />

Hot/Cold Ratio= 80%<br />

<strong>Motor</strong> Stopped after running Rated Load<br />

TCused_end= 0%<br />

0<br />

0 30 60 90 120 150 180<br />

Time in Minutes<br />

MOTOR STOPPED<br />

Hot/Cold Safe Stall Ratio<br />

Ieq = ---------------- 1– --------hot<br />

× 100%<br />

ol_pkp cold<br />

FIGURE 5–15: Thermal Model Cooling<br />

(EQ 5.5)<br />

(EQ 5.6)<br />

0<br />

0 30 60 90<br />

Time in Minutes<br />

120 150 180<br />

808705A2.CDR<br />

The motor manufacturer may provide thermal limit information for a hot/cold motor. The<br />

<strong>469</strong> thermal model adapts for these conditions if the HOT/COLD SAFE STALL RATIO settings<br />

is programmed. This settings value dictates the level of thermal capacity used the relay will<br />

settle at for current levels below the OVERLOAD PICKUP LEVEL. When the motor is running<br />

5–56 <strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL<br />

Thermal Capacity Used<br />

Thermal Capacity Used<br />

100<br />

75<br />

50<br />

25<br />

100<br />

75<br />

50<br />

25<br />

Cool Time Constant= 15min<br />

TCused_start= 85%<br />

Hot/Cold Ratio= 80%<br />

Ieq/Overload Pickup= 100%<br />

100% LOAD<br />

Cool Time Constant= 30min<br />

TCused_start= 100%<br />

Hot/Cold Ratio= 80%<br />

<strong>Motor</strong> Overload<br />

TCused_end= 0%<br />

0<br />

0 30 60 90 120 150 180<br />

Time in Minutes<br />

MOTOR TRIPPED