CHAPTER 5: SETTINGS<br />

5.13.2 Analog Inputs 1 to 4<br />

Table 5–3: Analog Output Parameter Selection Table<br />

PARAMETER NAME RAN<strong>GE</strong> / UNITS STEP DEFAULT<br />

MWhrs 0.000 to 999999.999 MWhrs 0.001 50.000 100.000<br />

Analog In Diff 1-2 –50000 to +50000 1 0 100<br />

Analog In Diff 3-4 –50000 to +50000 1 0 100<br />

Torque 0 to 999999.9 0.1 0 100<br />

PATH: SETTINGS S12 ANALOG I/O ANALOG INPUT 1(4)<br />

<br />

ANALOG [<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

ANALOG INPUT 1:<br />

Disabled<br />

ANALOG INPUT 1<br />

NAME:<br />

ANALOG INPUT 1<br />

UNITS:<br />

ANALOG INPUT 1<br />

MINIMUM: 0<br />

ANALOG INPUT 1<br />

MAXIMUM: 100<br />

BLOCK ANALOG<br />

INPUT 1<br />

ANALOG INPUT 1<br />

ALARM: Off<br />

ASSIGN ALARM<br />

RELAYS:<br />

ANALOG INPUT 1<br />

ALARM<br />

ANALOG INPUT 1<br />

ALARM<br />

ANALOG INPUT 1<br />

ALARM<br />

ANALOG INPUT 1<br />

ALARM<br />

ANALOG INPUT 1<br />

TRIP: Off<br />

ASSIGN TRIP<br />

RELAYS:<br />

MIN. MAX<br />

Range: Disabled, 4-20 mA, 0-20 mA, 0-<br />

1 mA<br />

Range: 12 alphanumeric characters<br />

Range: 6 alphanumeric characters<br />

Range: –50000 to 50000 in steps of 1<br />

Range: –50000 to 50000 in steps of 1<br />

Range: 0 to 5000 s in steps of 1<br />

Range: Off, Latched, Unlatched<br />

Range: Alarm, Alarm & Auxiliary2,<br />

Alarm & Aux2 & Aux3, Alarm &<br />

Auxiliary3, Auxiliary2, Aux2 &<br />

Aux3, Auxiliary3, None<br />

Range: –50000 to 50000 in steps of 1<br />

Units reflect ANALOG INPUT 1<br />

UNITS above<br />

Range: Over, Under<br />

Range: 0.1 to 300.0 s in steps of 0.1<br />

Range: On, Off<br />

Range: Off, Latched, Unlatched<br />

Range: Trip, Trip & Auxiliary2, Trip &<br />

Aux2 & Aux3 Trip & Auxiliary3<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 5–93