06.05.2013 Views

Multilin 469 Motor Management Relay ... - GE Digital Energy

Multilin 469 Motor Management Relay ... - GE Digital Energy

Multilin 469 Motor Management Relay ... - GE Digital Energy

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

5.2.8 Installation<br />

CHAPTER 5: SETTINGS<br />

• CLEAR ANALOG I/P MIN/MAX: The minimum and maximum analog input values are<br />

stored for each analog input. These minimum and maximum values may be cleared at<br />

any time.<br />

• CLEAR TRIP COUNTERS: There are counters for each possible type of trip. This<br />

command clears these counters.<br />

• PRESET DIGITAL COUNTER: When one of the assignable <strong>Digital</strong> Inputs is configured as<br />

“Counter”, this command presets the counter. If the counter is an incrementing type,<br />

setting the preset value to “0” effectively resets the counter.<br />

• CLEAR EVENT RECORDER: The event recorder saves the last 256 events,<br />

automatically overwriting the oldest event. If desired, this command can clear all<br />

events to prevent confusion with old information.<br />

PATH: SETTINGS S1 <strong>469</strong> SETUP INSTALLATION<br />

<br />

INSTALLATION [<br />

MESSA<strong>GE</strong><br />

RESET MOTOR<br />

INFORMATION: No<br />

RESET STARTER<br />

INFORMATION: No<br />

Range: No, Yes<br />

Range: No, Yes<br />

These commands clear various informative and historical data when the <strong>469</strong> is first<br />

applied on a new installation.<br />

• RESET MOTOR INFORMATION: Counters for number of motor starts and emergency<br />

restarts can be viewed in actual values. The <strong>469</strong> also learns various motor<br />

characteristics through motor operation. These learned parameters include<br />

acceleration time, starting current, and starting thermal capacity. Total motor running<br />

hours may also be viewed in actual values. On a new installation or if new equipment<br />

is installed, all this information can be reset with this settings.<br />

• RESET STARTER INFORMATION: The total number of starter operations can be viewed<br />

in actual values. Use this settings to clear this counter on a new installation or if<br />

maintenance work is done on the breaker or contactor.<br />

5–16 <strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!