CHAPTER 5: SETTINGS<br />

5.14.2 Pre-Fault Setup<br />

PATH: SETTINGS S13 <strong>469</strong> TESTING PRE-FAULT SETUP<br />

PRE-<br />

FAULT []<br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

MESSA<strong>GE</strong><br />

PRE-FAULT CURRENT<br />

PHASE A: 0.00 x<br />

PRE-FAULT CURRENT<br />

PHASE B: 0.00 x<br />

PRE-FAULT CURRENT<br />

PHASE C: 0.00 x<br />

PRE-FAULT GROUND<br />

CURRENT: 0.0 A<br />

PRE-FAULT VOLT-<br />

A<strong>GE</strong>S<br />

PRE-FAULT CURRENT<br />

LAGS VOLTA<strong>GE</strong>: 0°<br />

PRE-FAULT DIFF<br />

AMPS<br />

PRE-FAULT STATOR<br />

RTD TEMP: 40°C<br />

PRE-FAULT BEARING<br />

RTD TEMP: 40°C<br />

PRE-FAULT OTHER<br />

RTD TEMP: 40°C<br />

PRE-FAULT AMBIENT<br />

RTD TEMP: 40°C<br />

PRE-FAULT SYSTEM<br />

FREQUENCY: 60.0<br />

PRE-FAULT ANALOG<br />

INPUT 1: 0%<br />

PRE-FAULT ANALOG<br />

INPUT 2: 0%<br />

PRE-FAULT ANALOG<br />

INPUT 3: 0%<br />

PRE-FAULT ANALOG<br />

INPUT 4: 0%<br />

Range: 0.00 to 20.00 x CT in steps of<br />

0.01<br />

Range: 0.00 to 20.00 x CT in steps of<br />

0.01<br />

Range: 0.00 to 20.00 x CT in steps of<br />

0.01<br />

Range: 0.0 to 5000.0 A in steps of 0.1<br />

Range: 0.00 to 1.10 x RATED in steps of<br />

0.01<br />

Range: 0 to 359° in steps of 1<br />

Range: 0.00 to 1.10 x RATED in steps of<br />

0.01<br />

Range: –50 to 250°C in steps of 1<br />

Range: –50 to 250°C in steps of 1<br />

Range: –50 to 250°C in steps of 1<br />

Range: –50 to 250°C in steps of 1<br />

Range: 45.0 to 70.0 Hz in steps of 0.1<br />

Range: 0 to 100% in steps of 1<br />

Range: 0 to 100% in steps of 1<br />

Range: 0 to 100% in steps of 1<br />

Range: 0 to 100% in steps of 1<br />

The values entered under Pre-Fault Values will be substituted for the measured values in<br />

the <strong>469</strong> when the simulation mode is “Simulate Pre-Fault”.<br />

<strong>469</strong> MOTOR MANA<strong>GE</strong>MENT RELAY – INSTRUCTION MANUAL 5–99