B Not Used 3000 6 1½” / 467<br />

C Not Used 3000 5 1” / 57<br />

D Not Used 4000 5 1” / 57<br />

E Not Used 4000 4 1½” / 467<br />

1. Maximum Slump for Concrete Containing High-Range Water-Reducing Admixture: 8<br />

inches after admixture is added to concrete with initial slump of 2- to 4-inch.<br />

D. Slab-on-Grade: Proportion normal-weight concrete mix as follows:<br />

1. Paste Fraction: 25 to 38% by volume<br />

a. Paste fraction is the ratio of paste volume to the total mix volume.<br />

b. Paste is defined as the cementitious materials + entrained air + water.<br />

2. Mortar Fraction: 55 to 57% by volume<br />

a. Mortar Fraction is the ratio of Mortar to the total mix volume.<br />

b. Mortar is defined as the Paste + W.<br />

c. Where W(fine aggregate) is that portion of the combined aggregates passing the #8<br />

sieve.<br />

3. Coarseness Factor: 50 to 75%<br />

a. Coarseness Factor is defined as: Q / (Q + I)<br />

b. Where Q (coarse aggregate) is the percentage of the combined aggregate greater<br />

than 3/8-inch <strong>and</strong> I (intermediate aggregate) is the percentage of the combined aggregate<br />

between the 3/8-inch <strong>and</strong> #8 sieves.<br />

4. Workability Factor: 32 to 42%<br />

a. Workability factor is defined as: W / (Q + I + W)<br />

E. Maximum Water-Cementitious Materials Ratio: 0.45.<br />

F. Air Content: Add air-entraining admixture at manufacturer's prescribed rate to result in concrete<br />

at point of placement having an air content of 2 to 4 percent, unless otherwise indicated.<br />

1. Exterior Concrete: Add air-entraining admixture at manufacturer's prescribed rate to result<br />

in concrete at point of placement having an air content as follows within a tolerance<br />

of plus 1 or minus 1.5 percent, unless otherwise indicated:<br />

a. Air Content: 5.5 percent for 1-1/2-inch nominal maximum aggregate size.<br />

G. Do not air entrain concrete to trowel-finished interior floors <strong>and</strong> suspended slabs. Do not allow<br />

entrapped air content to exceed 3 percent.<br />

H. Limit water-soluble, chloride-ion content in hardened concrete to 0.15 percent by weight of<br />

cement.<br />

I. Admixtures: Use admixtures according to manufacturer's written instructions.<br />

1. Use water-reducing admixture or high-range water-reducing admixture (superplasticizer)<br />

in concrete, as required, for placement <strong>and</strong> workability.<br />

2. Use water-reducing <strong>and</strong> retarding admixture when required by high temperatures, low<br />

humidity, or other adverse placement conditions.<br />

Cast-in-Place Concrete 03 30 00 - 7<br />