26 05 19 LOW VOLTAGE ELECTRICAL POWER CONDUCTORS & CABLES<br />

1.00 GENERAL<br />

1.01 WORK INCLUDED<br />

A. Furnish labor, materials, equipment <strong>and</strong> incidentals necessary to install 600 volt wires <strong>and</strong><br />

cables. Electrical work shall be in accordance with Section 26 05 00, COMMON WORK<br />

RESULTS FOR ELECTRICAL.<br />

B. Work shall include building wire, cable, wiring connections <strong>and</strong> terminations, <strong>and</strong> modular<br />

wiring systems.<br />

1.02 QUALITY ASSURANCE: TESTING<br />

Megger test circuits for continuity <strong>and</strong> ground. Verify phasing at connection points. Torque test<br />

conductor connections <strong>and</strong> terminations to the Manufacturer's recommended values. Megger tests<br />

shall be performed by a testing company with a minimum of 10 years experience. All low voltage<br />

cables shall be verified by use of telephone communications.<br />

1.03 SUBMITTALS<br />

Submittals shall be in accordance with Section 01 33 00, SUBMITTALS <strong>and</strong> shall include:<br />

A. Low voltage wire<br />

B. Ground wire<br />

1.04 STANDARDS<br />

The applicable provisions of the following st<strong>and</strong>ards shall apply as if written here in their entirety:<br />

ICEA S-19-81/NEMA WC-3<br />

ICEA S-61-402/NEMA WC-5<br />

Rubber-Insulated Wire <strong>and</strong> Cable for the Transmission <strong>and</strong><br />

Distribution of Electrical Energy<br />

Thermoplastic-Insulated Wire <strong>and</strong> Cable for the Transmission <strong>and</strong><br />

Distribution of Electrical Energy<br />

1.05 DELIVERY AND STORAGE<br />

Deliver cable <strong>and</strong> wire to the project site in the original packages. Conductors with damaged<br />

insulation or exposed nylon jacketing shall not be permitted.<br />

2.00 PRODUCTS<br />

2.01 CONDUCTORS AND CABLES<br />

A. CONDUCTORS: Soft-drawn, annealed copper with a conductivity of not less than that of 98%<br />

pure copper bearing the U.L. label. The minimal size shall be #12 unless specified otherwise<br />

on plans. Conductors #8 or larger <strong>and</strong> conductors #14 shall be str<strong>and</strong>ed. Utilize single<br />

conductors.<br />

Low Voltage Electrical Power Conductors & Cables 26 05 19-1<br />