28.04.2015 Views

final bid specs 09328.pdf - Freese and Nichols, Inc.

final bid specs 09328.pdf - Freese and Nichols, Inc.

final bid specs 09328.pdf - Freese and Nichols, Inc.

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

A. Description: Microelectronic monitor module listed for use in providing a system address for<br />

listed alarm-initiating devices for wired applications with normally open contacts. Provide UL<br />

Listed End-of-Line Resistors where installed.<br />

2.07 DIGITAL ALARM COMMUNICATOR TRANSMITTER<br />

A. Listed <strong>and</strong> labeled according to UL 632. Transmitter shall be integrated within the fire alarm<br />

control panel thus not requiring a separate enclosure or power source.<br />

B. Functional Performance: Unit receives an alarm, supervisory, or trouble signal from the<br />

FACP, <strong>and</strong> automatically captures one or two telephone lines <strong>and</strong> dials a preset number for a<br />

remote central station. When contact is made with the central station(s), the signal is transmitted.<br />

The unit shall supervise two telephone lines. If service on either line is interrupted for<br />

longer than 45 seconds, the unit initiates a local trouble signal <strong>and</strong> transmits a signal indicating<br />

loss of telephone line to the remote alarm receiving station over the remaining line. When<br />

telephone service is restored, unit automatically reports that event to the central station. If<br />

service is lost on both telephone lines, the local trouble signal is initiated.<br />

C. Secondary Power: Integral rechargeable battery <strong>and</strong> automatic charger shall be provided by<br />

the FACP.<br />

D. Self-Test: Conducted automatically every 24 hours with report transmitted to central station.<br />

E. Monitoring Service: The fire alarm contractor shall coordinate with the Owner’s selected<br />

monitoring service provider <strong>and</strong> provide all labor, material, <strong>and</strong> devices necessary to achieve<br />

successful monitoring of the building fire alarm system. The cost for the phone lines <strong>and</strong><br />

maintaining the phone service shall be the owner’s responsibility.<br />

2.08 WIRE AND CABLE<br />

A. Wire <strong>and</strong> cable for fire alarm systems shall be UL listed <strong>and</strong> labeled as complying with<br />

NFPA 70, Article 760 <strong>and</strong> shall be in accordance with the manufacturer’s recommendations.<br />

B. Signaling Line Circuits: Twisted, shielded pair, size as recommended by system manufacturer.<br />

Shielding shall only be required if required or recommended by the system manufacturer.<br />

C. Non-Power-Limited Circuits: Solid-copper conductors with 600-V rated, 75 deg C, colorcoded<br />

insulation.<br />

1. Low-Voltage Circuits: No. 16 AWG, minimum for SLC’s <strong>and</strong> No. 12 AWG for NAC’s.<br />

2. Line-Voltage Circuits: No. 12 AWG, minimum.<br />

3.00 EXECUTION<br />

3.01 EQUIPMENT INSTALLATION<br />

A. Manual Pull Stations:<br />

1. Provide a manual pull station near the FACP as directed by the AHJ. Provide additional<br />

manual pull stations as required by the AHJ.<br />

B. Smoke detectors: Install smoke detector above FACP. Provide additional smoke detectors<br />

as required by the AHJ. Installation shall conform to NFPA 72.<br />

C. Audible Alarm-Indicating Devices: Install in locations as required to achieve at least 15dBA<br />

above the average ambient sound level or 5 dBA above the maximum sound level having a<br />

duration of at least 60 seconds, whichever is greater, measured 5 feet above the floor in the<br />

occupiable area. Audible signaling shall meet the requirements of NFPA 72 4-3.2 “Public<br />

Mode Audible Requirements”.<br />

D. Visible Alarm-Indicating Devices: Install wall-mounted devices such that the entire lens is not<br />

less than 80 inches <strong>and</strong> not greater than 96 inches above the finished floor. Alternatively,<br />

ceiling-mounted devices may be used. Visible signaling shall meet the requirements of NFPA<br />

Fire Alarm <strong>and</strong> Detection System 13 85 10-7<br />

DPR09328

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!