B. Manufacturer shall have produced similar electrical equipment for a minimum period of five<br />

(5) years. When requested by the engineer, an acceptable list of installations with similar<br />

equipment shall be provided demonstrating compliance with this requirement.<br />

2.00 PRODUCTS<br />

2.01 PANELBOARDS<br />

A. Panelboards shall consist of a box, front, interior <strong>and</strong> circuit protective devices <strong>and</strong> shall be<br />

manufactured in accordance with NEMA PB1 <strong>and</strong> bearing the applicable U.L. labels.<br />

B. Panelboards shall be four wire, three phase as scheduled or required. Panelboards shall be<br />

NEMA 1 for air conditioned spaces, NEMA 12 Steel for ventilated areas <strong>and</strong> NEMA 3R for<br />

exterior locations <strong>and</strong> suitable for surface mounting. Panelboards shall contain sequence<br />

style busing <strong>and</strong> full capacity neutral, composed of an assembly of bolt-on, molded case,<br />

automatic breakers with thermal <strong>and</strong> an instantaneous, magnetic trip in each pole <strong>and</strong> a tripfree<br />

position separate from either the "On" <strong>and</strong> the "Off" positions. Two (2) <strong>and</strong> three (3) pole<br />

circuit breakers shall simultaneously open all poles. Circuit breakers, molded case <strong>and</strong><br />

branch circuits shall be in accordance with Fed. Spec. W-C-375.<br />

C. The voltage rating, phase, number of wires <strong>and</strong> ampere rating shall be as indicated <strong>and</strong><br />

scheduled on the plans.<br />

D. The panelboard box shall be fabricated of code gauge, galvanized sheet steel in accordance<br />

with U.L. st<strong>and</strong>ards <strong>and</strong> have turned edges around the front for rigidity <strong>and</strong> frontal clamping.<br />

Provide st<strong>and</strong>ard knockouts on the panel enclosures.<br />

E. The panelboard front shall be fabricated of sheet steel <strong>and</strong> finished with a baked on gray<br />

enamel over a rust inhibitor. Each front shall have a door mounted on semi-concealed hinges<br />

with a cylinder lock, an index card <strong>and</strong> a card holder. Panelboard locks shall be master<br />

keyed, with two (2) keys furnished for each panel board. Index cards shall be properly<br />

typewritten.<br />

F. The interior of the panelboard shall consist of a factory-assembled, rigid frame supporting the<br />

rectangular bus, the mains <strong>and</strong> the neutral bar.<br />

G. Busings shall be tin-plated copper <strong>and</strong> arranged for sequential phasing throughout. The bus<br />

bar shall be sized so that the temperature rise is limited in accordance with NEMA st<strong>and</strong>ards.<br />

The insulated neutral bar shall be located at the opposite end of the structure from the mains.<br />

H. Panelboards shall have either solderless lugs or a main circuit protective device as<br />

scheduled. Each enclosure shall have grounding lugs <strong>and</strong> uninsulated equipment grounding<br />

terminals.<br />

2.02 CIRCUIT BREAKERS<br />

A. Panelboards shall be equipped with circuit breakers.<br />

B. Circuit breakers shall be molded case, bolt in type. Series rating of breakers is not acceptable.<br />

C. Single pole circuit breakers serving fluorescent lighting loads shall have the SWD marking.<br />

Circuit breakers serving air conditioning branch loads shall be U.L. listed as type HACR.<br />