11. Install conduit other than PVC with threaded couplings <strong>and</strong> other threaded fittings.<br />

Threadless, or clamp type fittings shall not be used on metallic conduit. Rigid aluminum<br />

conduit shall have each set of threads coated with an oxidation inhibitor, Ilsco, De-Ox, ITT<br />

Noalox, Blackburn Contax or approved equal.<br />

12. Use PVC coated, rigid aluminum, factory elbows for bends in PVC conduit.<br />

13. Use suitable conduit caps to protect installed conduit against entry of dirt <strong>and</strong> moisture.<br />

14. Use watertight hubs to fasten conduit to metal boxes, etc. in wet or damp locations per<br />

the National Electrical Code.<br />

15. Install a pulling string in empty (spare) conduit, except sleeves <strong>and</strong> nipples, <strong>and</strong> leave for<br />

future pulling as applicable.<br />

D. TERMINATIONS<br />

1. Use threaded hubs for termination of conduits. Locknut termination of conduits shall not<br />

be used on this project.<br />

2. Conduit terminations shall not penetrate the top of NEMA 4X <strong>and</strong> NEMA 3R enclosures.<br />

E. HAZARDOUS AREAS<br />

1. Install conduit seals at all penetrations to hazardous areas, as defined by the NEC <strong>and</strong> as<br />

shown on the plans. Install additional seal-type fittings within the hazardous area in<br />

accordance with the requirements of the NEC Article 500.<br />

2. Install dam <strong>and</strong> sealing compound per the seal Manufacturer's instructions.<br />

3. Provide flexible conduit which is listed for use in hazardous areas. Conduit, flexible<br />

conduit, fittings <strong>and</strong> all other materials shall be listed for use in a Class I Division 2<br />

Group(s) C&D atmosphere.<br />

END OF SECTION<br />