will occur as a result of overflow from the equipment drain pan or stoppage in the condensate<br />

drain piping. One of the following methods shall be used.<br />

1. An auxiliary drain pan with a separate drain shall be provided under the coils on which<br />

condensation will occur. The auxiliary pan drain shall discharge to conspicuous point of<br />

disposal to alert occupants in the event of a stoppage of the primary drain, The pan shall<br />

have a minimum depth of 1.5 inches (38 mm), shall not be less than 3 inches (76 mm)<br />

larger than the unit of the coil dimensions in width <strong>and</strong> length <strong>and</strong> shall be constructed of<br />

corrosion-resistant material. Metallic pans shall have a minimum thickness of not less<br />

than 0.0276 (0.7 mm) galvanized sheet metal. Nonmetallic pans shall have a minimum<br />

thickness of not less than 0.0625 inch (1.6mm).<br />

E. Electric Coil: Helical, nickel-chrome, resistance-wire heating elements with refractory ceramic<br />

support bushings; automatic-reset thermal cutout; built-in magnetic contactors; manualreset<br />

thermal cutout; airflow proving device; <strong>and</strong> one-time fuses in terminal box for overcurrent<br />

protection.<br />

F. Fan <strong>and</strong> Motor: Centrifugal fan, directly driven by multispeed, electric motor with integral<br />

overload protection; resiliently mounted.<br />

G. Filters: Permanent, cleanable 80-85% efficient located in return air grille.<br />

2.03 AIR-COOLED, COMPRESSOR-CONDENSER COMPONENTS<br />

A. Casing: Steel, finished with baked enamel, with removable panels for access to controls,<br />

weep holes for water drainage, <strong>and</strong> mounting holes in base. Provide brass service valves, fittings,<br />

<strong>and</strong> gage ports on exterior of casing.<br />

B. Compressor: Hermetically sealed with crankcase heater <strong>and</strong> mounted on vibration isolation.<br />

Compressor motor shall have thermal- <strong>and</strong> current-sensitive overload devices, start capacitor,<br />

relay, <strong>and</strong> contactor.<br />

1. Compressor Type: Scroll.<br />

2. Two-speed compressor motor (if scheduled) with manual-reset high-pressure switch <strong>and</strong><br />

automatic-reset low-pressure switch.<br />

C. Refrigerant Coil: Copper tube, with mechanically bonded aluminum fins, complying with<br />

ARI 210/240, <strong>and</strong> with liquid subcooler.<br />

D. Fan: Aluminum-propeller type, directly connected to motor.<br />

E. Motor: Permanently lubricated, with integral thermal-overload protection.<br />

F. Low Ambient Kit: Permits operation down to 0 deg F.<br />

2.04 ACCESSORIES<br />

A. Thermostat: Low voltage, programmable electronic thermostat, with the following features:<br />

1. Password protected 7-day program with night setback <strong>and</strong> instant override for 1 to 3 hour<br />

(adjustable) operation<br />

2. Digital display indicating:<br />

a. Day of week<br />

b. Room temperature<br />

c. Operating Mode<br />

Split System Air Conditioning Units 23 81 26 - 3<br />

DPR09328